Output
Loss–of–Signal
: Sets the Analog Output value used by the sensor during a loss of signal. When a signal is restored,
measurement resumes.
Hold Last Value—The Analog Output holds the last value indefinitely during a loss of signal.
3.5 mA (0 V)—The Analog Output switches to this value 2 seconds after a loss of signal. For Voltage models, this is 0
V. (Default)
20.5 mA (10.5 V/5 V)—The Analog Output switches to this value 2 seconds after a loss of signal. For Voltage models,
this is 10.5 V.
Averaging: Use this menu to set the number of measurements that are averaged together for the analog output.
Increasing the averaging improves repeatability but increases the total response speed. The default is 1. The filter can be
set to 1, 2, 4, 8, 16, 32, 64, or 128. The total response time is shown under Response Time.
Response Time
Calculates the total response time, taking into account the general response speed and averaging.
Response Speed
Analog Output Filter Setting
1
2
4
8
16
32
64
128
Analog Output Spec (ms)
Fast
16
32
64
128
256
512
1024
2048
Medium
80
160
320
640
1280
2560
5120
10,240
Slow
200
400
800
1600
3200
6400
1280
2560
The following are the parameters on the Discrete 1 tab on the Sensor Settings pane.
Output Mode
Select
Switch Point
or
Window
.
Switch Point
: The distance at which the switch point threshold is placed.
Window
: Define two set points to create window limits.
Distance Settings
Define the set point(s) and the hysteresis.
Output Settings
NO/NC
: Select
Normally Open
or
Normally Closed
from the list.
On Delay
: Set an on delay in milliseconds. The maximum time is 60,000 ms.
Off Delay
: Set an off delay in milliseconds. The maximum time is 60,000 ms.
Response Time
Calculates the total response time, taking into account the general response speed and on or off delays.
Response Speed
Discrete Output ON Spec (ms)
Discrete Output OFF Spec (ms)
Fast
50
50
Medium
100
200
Slow
250
550
The following are the parameters on the Discrete 2 tab on the Sensor Settings pane. This tab is available for dual discrete
models.
Output Mode
Select
Switch Point
,
Window
,
Complementary
, or
Pulse Pro/PFM
.
Switch Point
: Set a single switch point for the output to change.
Window
: Define two setpoints to create window limits.
Complementary
: Output 2 will be the opposite of Output 1.
Pulse Pro/PFM
: Pulse Pro/PFM output to interface with Banner lights or a PLC with PFM inputs.
Analog
Table 2.
Discrete 1 Tab
4.4.3
Discrete
Table 3.
Discrete 2 Tab
4.4.4