Banner Q45 Setup Manual Download Page 9

9

Troubleshooting

Problem

Possible Causes / Solutions

Directional Counts are not changing

Sensors may not be properly aligned. Realign the sensors.
Batteries may need to be replaced

Directional Count is opposite of expectation

Sensors pair may be installed in reverse order. Verify sensors A and B are installed in the correct order.

Sensors are double counting

Sensors may not be properly aligned. Realign the sensors.
Adjust the sensor height to avoid carts and other objects triggering the sensors.

Sensors missing directional counts or over 
counting

People may be entering side-by-side, causing the sensors to view a single count instead of two people. 
People stopping in the middle of the beam path may block others coming through and being counted. 
If someone walks into the beam path without going through completely, stops, then turns around, the 
person may not have been counted properly.
Recommend instructing people to walk through in a single file pattern and not to stop in front of the 
sensor’s beam path.

Counts reset unexpectedly

Pushing the back arrow on the Operator Interface clears all the counts, similar to the daily reset.

All counts reset overnight

The DXM Controller is programmed to reset all counts at 2 AM Central (observing DST).
Contact your local distributor or Banner Engineering’s technical support team at 1-800-203-5616 for 
assistance on changing the reset schedule.

Operator Interface no longer displays the 
counts

After the DXM Controller is rebooted, a delay of 5 minutes may occur before counts are displayed.
The Operator Interface may not be communicating with the DXM Controller. Check the LED above the 

 (check mark) button. If the LED flashes red, change the positioning of the DXM Controller or Operator 

Interface so that they are closer to each other. The LED should flash green when the Operator Interface 
is communicating to the DXM Controller. If the indicator LED does not begin to flash green, contact your 
local distributor or Banner Engineering’s technical support team at 1-800-203-5616.

Sensor’s red LED is flashing

Sensors are not communicating with the DXM Controller 
Change the positioning of the DXM Controller to improve radio signal. The indicator LEDs should flash 
green when the Sensors are communicating to the DXM Controller. If the indicator LEDs do not begin to 
flash green, contact your local distributor or Banner Engineering’s technical support team at 1-800-203-
5616.

Wireless TL70 Indicator Light is not lighting up After the DXM Controller reboots or cycles power, a delay of up to five minutes may occur before LEDs 

turn on.
The TL70 Wireless Indicator Light may not be communicating with the DXM Controller. Remove the light 
module above the base by rotating the base counterclockwise and pulling it off of the segments, the 
lines on the notches should align. Verify the LED is flashing green. If the LED is flashing red, change the 
positioning of the DXM Controller or TL70 Wireless Indicator Light to improve communication. The LED 
should flash green when the Indicator Light is communicating to the DXM Controller. If the indicator LEDs 
do not begin to flash green, contact your local distributor or Banner Engineering’s technical support team 
at 1-800-203-5616.

Summary of Contents for Q45

Page 1: ...217889 Rev A Occupancy Solution Kit Total Count TC Setup Guide ...

Page 2: ...ator includes bracket and power supply Q45 Sensor Pair includes AA batteries DXM Controller Not Shown mounted inside building Direct Select Operator Interface includes C battery Power Supply Reflector Pair pre mounted on bracket Tools Needed Tape measure Phillips screwdriver ...

Page 3: ...M Controller in a secure location outside of any metal cabinets or enclosures The Q45 Sensor Pair detects whether a person is entering or exiting the monitored area The Sensor Pair comes with two sensors Sensor A and Sensor B Mount the Q45 Sensor Pair according to Banner s suggested mounting instructions on page 6 The Direct Select Operator Interface displays the total count of people in the monit...

Page 4: ...e four corner screws Do not over tighten 5 If the indicator LEDs do not automatically begin flashing turn on the sensor by pressing and holding the button for five seconds until the LED to the right of the button flashes 1 Loosen the clamp plate with a small Phillips screwdriver and lift the cover 2 Using a small Phillips screwdriver insert the tip into the small hole in the battery holder and pry...

Page 5: ...or or Banner Engineering s Technical Support team at 1 800 203 5616 for more options or refer to our Troubleshooting section on page 9 When mounting the Q45 Sensor Pairs on the inside of the door 1 Place Sensor A closest to the L section of the mounting bracket 2 Place Sensor B on the remaining mounting hole 3 Thread the black locknut onto the bases and hand tighten 4 Connect the cable from Sensor...

Page 6: ...oors For occupancy monitoring in areas with inward opening doors Banner recommends mounting the devices on the inside of the door far enough from the door that the door does not trip the sensor pair when opening Two mounting options are shown I and II Mounting I is preferred to keep the sensors and reflectors from obstructing the area Mounting II is possible when no other mounting options are avai...

Page 7: ...s seeing Reflector B Rotate Sensor A outward until it is seeing Reflector A If the sensors will not optically align to their reflector refer to the Troubleshooting section for more information or contact your local distributor or Banner Engineering for assistance 7 Confirm optical alignment by blocking reflector B with a hand or opaque object at the reflector The amber alignment indicator on senso...

Page 8: ...Registers menu and press ENTER Highlight Occupancy Limit and press ENTER Enter your desired Occupancy Limit 1 Using the up and down arrow buttons select the first digit for the limit and press ENTER to set the first digit 2 Use the up and down arrows to set the second digit and press ENTER 3 Repeat if you are adding a third digit 4 Press ENTER once more to highlight SEND and press ENTER to confirm...

Page 9: ...r before counts are displayed The Operator Interface may not be communicating with the DXM Controller Check the LED above the check mark button If the LED flashes red change the positioning of the DXM Controller or Operator Interface so that they are closer to each other The LED should flash green when the Operator Interface is communicating to the DXM Controller If the indicator LED does not begi...

Page 10: ...f directed to by your IT department Setting a Static IP Address To define a specific IP address of your choosing 1 On the DXM use the arrows and move to the System Config menu Press ENTER 2 Use the arrow keys to select the Ethernet menu Press ENTER 3 Highlight the DHCP selection and press ENTER Set DHCP to OFF 4 The system will request a restart press ENTER to confirm 5 Follow steps 1 and 2 to ent...

Page 11: ...ler s LCD On the DXM s main menu scroll to System Info and then press ENTER twice to view the seven digit serial number at the bottom of the information list 3 Enter all seven digits into the DXM Serial entry field on Banner CDS 4 Verify that Configuration is set to Solutions and select Occupancy for the Kit Type This allows the Banner CDS application to automatically create Dashboard layouts and ...

Page 12: ...nch screw mounts Used on multiple mounting brackets 31 75 mm 1 25 inch diameter No fasteners included LMB30LP Used with the TL70 Wireless Indicator Light Low profile 30 mm mounting hole 300 series stainless steel No fasteners included SMBAMS30RA Used with the Q45 Sensor Pair one per sensor Right angle SMBAMS series bracket 30 mm hole for mounting sensors Articulation slots for 90 rotation 12 gauge...

Reviews: