L-GAGE
®
LT7 Long-Range Time-of-Flight Sensor
P/N 120244
9
Banner Engineering Corp.
•
Minneapolis, MN U.S.A.
www.bannerengineering.com • Tel: 763.544.3164
Main
Menu
Procedure
Example Displays
Result
TEACH-IN
(Setup)
–
Discrete
TEACH 1.2
• From Output 1 menu, press
to teach 1.2 limit.
• Repeat process on previous
page for limit 1.2.
TEACH1.2
<12000>
• Sensor again displays TEACH options for selected output.
Hysteresis
• Press to select
hysteresis function.
HYST 1
< ±005>
• Blinking cursor indicates active digit (beginning with right-
hand digit).
• Factory default setting is ± 005 (the minimum setting).
• Maximum hysteresis setting is ± 254 mm or ± 9.99".
• Press or to
decrease or increase value
of each digit.
• Press to select and
move one digit left.
HYST 1
±254
• When cursor is at left-hand
digit and value is correct,
press
HYST 1
<±254>
If value
is valid
– or –
HYST 1
LIMITED!
If value is
outside
accepted limits
• Sensor saves setting and returns to Hyst 1 menu level.
• Use Escape function to go
up one menu level, or use
or to return to
other Output 1 functions.
• Repeat as desired for Output 2.
• Teach processes for Outputs 1 and 2 are identical.
• If value is outside accepted limits, sensor does not save
new setting.
TEACH-IN
(Setup)
–
Analog;
Copy
Discrete
Limits
TEACH Analog output individual limits using the same procedures as described above (except that the Analog output has no
hysteresis option). The Analog output has one unique function – copying the Discrete output limits (Q1.1 and Q2.1); for this
procedure, see steps below.
• From TEACH-IN menu,
press and or
to scroll to Analog Teach.
TEACH-IN
<ANALOG>
• Sensor is ready to learn analog limits.
• Procedure is identical to teaching discrete limits, except
for copy/paste function.
• Select Analog mode, as for
discrete limits.
or to copy Q to A
COPY Q->A
<ENTER>
• Sensor is ready to copy discrete limits to Analog output.
• Press
• Press and to scroll
between options.
• Press to select
displayed option.
COPY Q->A
->Q1 & Q2
– or –
COPY Q->A
->Q2 & Q1
– or –
<300 mm
If discrete limits
are less than 300
mm apart
• The option selected, in combination with the selected
mode, determines the analog output slope.
For Mode 1 (positive slope):
Q1 & Q2
– Limit Q1.1 becomes A1 (4 mA);
Q2.1 becomes A2 (20 mA)
Q2 & Q1
– Limit Q1.1 becomes A2 (20 mA);
Q2.1 becomes A1 (4 mA)
For Mode 2 (negative slope), the above is reversed.
If discrete limits are not at least 300 mm apart, display
will show < 300 mm and sensor will not perform the copy
function.
���
���
���
���
���
���
���
���
���
���
���
���
���
���
���
���
���