iVuPlus sensor provides several tools to help diagnose communication issues when using Industrial Ethernet channel.
8.8.1 Ethernet Diagnostics
To verify Ethernet connectivity, please follow these steps:
• Verify that all the cables are connected and properly seated.
• Examine the small orange Ethernet link light located on the top of camera body, between the Pass/Fail and System Status LEDs. The
light should be either on or blinking.
• Go to the System > Logs > System Log page, and verify that the log entry indicates that the Ethernet link is up:
• Go to the System > Communications > Ethernet I/O page, and press on the Status button. Verify that the Ethernet Link Status is
"Connected", and that the link parameters, such as baud rate and duplex are as expected. For example:
iVu Plus User's Manual
142