Device description  • Connection elements 

40

Power Panel T30  User's manual V1.42 - Translation of the original documentation

The supply voltage is protected internally by a soldered fuse (see technical data) against overload. The device

must be sent to B&R for repairs if the fuse is destroyed in the event of error (fuse replacement).

Danger!

This device is only permitted to be supplied with protective extra-low voltage (PELV).
Protective earth (grounding clip on the device) and the GND connection of the power supply are con-

nected internally in the Power Panel.

Important!

The ground connection of the device must be low impedance and connected to ground (e.g. grounding

rail in the control cabinet) using a short path.

Summary of Contents for Power Panel T30

Page 1: ...Automation GmbH is not liable for technical editorial errors or incomplete information in this manual In addition B R Industrial Automation GmbH shall not be liable for incidental or consequential da...

Page 2: ...Table of contents 2 Power Panel T30 User s manual V1 42 Translation of the original documentation...

Page 3: ...dio and Automation Runtime dependencies 16 3 2 3 Surface resistance of the panel overlay 17 3 2 4 Surface resistance of the touch screen 17 3 3 Power Panel T30 4 3 variants 18 3 3 1 Order data 18 3 3...

Page 4: ...torage 75 5 1 11 Service page Update 77 5 1 12 Service page Backup Reset 81 5 1 13 Service page Security 82 5 1 14 Service page OPC UA 83 5 1 15 Service page Save Exit 85 5 1 16 Service page About Inf...

Page 5: ...TB6102 2 pin power supply connector 128 8 2 1 Order data 128 8 2 2 Technical data 128 8 3 Data storage devices 128 8 4 Cable accessories 128 9 International and national certifications 129 9 1 Overvi...

Page 6: ...Changed content Improved description of Hand button Harmonized technical data Changed tightening torque of retaining clips from 0 6 to 0 4 Nm Editorial changes and corrections 1 30 December 2016 Rest...

Page 7: ...gulations This also applies to all other devices connected to the system such as drives All tasks such as the installation commissioning and servicing of devices are only permitted to be carried out b...

Page 8: ...utions relevant to industrial control systems e g the provision of safety devices such as emergency stop etc must be observed in accordance with applicable national and international regulations This...

Page 9: ...tions that can damage electronic components very quickly The presence of corrosive gases is indicated by blackened copper surfaces and cable ends on existing installations When operated in dusty or mo...

Page 10: ...these safety guidelines and notices can result in death severe injury or substantial damage to property Caution Failure to observe these safety guidelines and notices can result in minor injury or dam...

Page 11: ...for harsh industrial environments 2 2 Flexibility Power Panel T30 devices are available in 4 different display sizes ranging from 4 3 to 10 1 see Type overview on page 14 A touch button is integrated...

Page 12: ...l documentation 2 3 Simple HMI The Power Panel T30 is a dedicated HMI device that can be operated in 2 different terminal modes Terminal as VNC client for VNC based HMI applications created in Automat...

Page 13: ...WQVGA resolution analog resistive touch screen landscape format aluminum white pinstripe Interfaces 2x Ethernet 10 100 Mbit s integrated switch 2x USB 2 0 Client software Integrated service page VNC c...

Page 14: ...20x 6PPT30 070x 20x 6PPT30 101x 20x Format Resolution Landscape format Portrait format Resolution WQVGA 480 x 272 VGA 640 x 480 WVGA 800 x 480 WSVGA 1024 x 600 WQVGA 272 x 480 VGA 480 x 640 WVGA 480...

Page 15: ...al V1 42 Translation of the original documentation 15 3 1 1 Compare Power Panel T30 variants Format Panel overlay Landscape format Portrait format Aluminum white Anthracite Aluminum white Anthracite 4...

Page 16: ...nd vertical U D axes in reference to the vertical axis of the display The specified viewing angles above always refer to the standard mounting orientation of the respective Power Panel Standard mounti...

Page 17: ...onitrile Sodium bisulphate Cutting oil Diesel oil Linseed oil Paraffin oil Ricinus oil Silicon oil Turpentine oil substitute Brake fluid Aviation fuel Gasoline Water Sea water Decon Sodium chloride 20...

Page 18: ...tware Integrated service page VNC client em bedded web browser 6PPT30 043K 20B Power Panel T30 4 3 portrait format CPU and memory 600 MHz ARM Cortex A8 512 MB onboard flash drive Display and touch scr...

Page 19: ...yer 10BASE T 100BASE TX Half duplex Yes Full duplex Yes Autonegotiation Yes Auto MDI MDIX Yes Interface IF3 Type USB 2 0 Variant Type A Current carrying capacity 0 5 A 1 Interface IF4 Type USB 2 0 Var...

Page 20: ...e Anthracite gray pinstripe Aluminum white pinstripe Anthracite gray pinstripe Dimensions Width 140 mm 96 mm Height 96 mm 140 mm Depth 38 3 mm Weight 0 3 kg Table Power Panel T30 4 3 variants Technica...

Page 21: ...Landscape format for 4 3 variants Shield attachment plate 140 96 R2 84 8 82 6 33 3 5 128 8 12 5 5 7 M5 6 23 138 7 Shield attachment plate see Mounting shield attachment plate for 4 3 Power Panel page...

Page 22: ...format for 4 3 variants Shield attachment plate 6 23 84 8 82 6 5 96 140 R 2 33 3 5 74 128 8 M5 12 5 138 7 Shield attachment plate see Mounting shield attachment plate for 4 3 Power Panel page 45 Dimen...

Page 23: ...0 Mbit s integrated switch 2x USB 2 0 Client software Integrated service page VNC client em bedded web browser 6PPT30 057L 20B Power Panel T30 5 7 portrait format CPU and memory 600 MHz ARM Cortex A8...

Page 24: ...Physical layer 10BASE T 100BASE TX Half duplex Yes Full duplex Yes Autonegotiation Yes Auto MDI MDIX Yes Interface IF3 Type USB 2 0 Variant Type A Current carrying capacity 0 5 A 1 Interface IF4 Type...

Page 25: ...Anthracite gray pinstripe Aluminum white pinstripe Anthracite gray pinstripe Dimensions Width 172 mm 140 mm Height 140 mm 172 mm Depth 47 8 mm Weight 0 5 kg Table Power Panel T30 5 7 variants Technica...

Page 26: ...original documentation 3 4 5 Dimensions Landscape format for 5 7 variants 172 140 R2 127 9 42 8 5 M5 112 9 159 8 27 8 13 8 12 5 5 1 0 70 139 26 27 0 145 72 1 02 Dimensions of the installation cutout...

Page 27: ...of the original documentation 27 Portrait format for 5 7 variants 140 172 R 2 127 9 13 8 5 42 8 M5 27 8 112 9 159 8 1 0 70 139 12 5 5 1 0 26 27 145 72 Dimensions of the installation cutout for this P...

Page 28: ...0 Mbit s integrated switch 2x USB 2 0 Client software Integrated service page VNC client em bedded web browser 6PPT30 070M 20B Power Panel T30 7 0 portrait format CPU and memory 600 MHz ARM Cortex A8...

Page 29: ...sical layer 10BASE T 100BASE TX Half duplex Yes Full duplex Yes Autonegotiation Yes Auto MDI MDIX Yes Interface IF3 Type USB 2 0 Variant Type A Current carrying capacity 0 5 A 2 Interface IF4 Type USB...

Page 30: ...m white pinstripe Anthracite gray pinstripe Dimensions Width 197 mm 140 mm Height 140 mm 197 mm Depth 47 8 mm Weight 0 6 kg Table Power Panel T30 7 0 variants Technical data 1 The clock frequency is 6...

Page 31: ...ginal documentation 31 3 5 5 Dimensions Landscape format for 7 0 variants 197 140 R2 112 9 184 8 27 8 5 42 8 127 9 13 8 12 5 5 5 1 0 70 138 9 26 27 0 1 170 73 M5 Dimensions of the installation cutout...

Page 32: ...n of the original documentation Portrait format for 7 0 variants 197 140 R 2 27 8 5 42 8 184 8 112 9 M5 127 9 13 8 70 0 138 92 1 1 0 26 27 170 73 12 5 5 Dimensions of the installation cutout for this...

Page 33: ...10 100 Mbit s integrated switch 2x USB 2 0 Client software Integrated service page VNC client embedded web browser 6PPT30 101N 20B Power Panel T30 10 1 portrait format CPU and memory 600 MHz ARM Corte...

Page 34: ...e 10 100 Mbit s Transfer Physical layer 10BASE T 100BASE TX Half duplex Yes Full duplex Yes Autonegotiation Yes Auto MDI MDIX Yes Interface IF3 Type USB 2 0 Variant Type A Current carrying capacity 0...

Page 35: ...white pinstripe Anthracite gray pinstripe Dimensions Width 276 mm 172 mm Height 172 mm 276 mm Depth 47 8 mm Weight 0 9 kg Table Power Panel T30 10 1 variants Technical data 1 The clock frequency is 6...

Page 36: ...6 5 Dimensions Landscape format for 10 1 variants 276 172 5 160 112 9 42 8 127 4 27 8 264 13 8 5 12 5 R 2 17 02 0 131 42 13 8 1 0 26 19 60 56 145 8 158 03 171 18 92 0 129 52 1 138 275 27 8 Dimensions...

Page 37: ...umentation 37 Portrait format for 10 1 variants 5 42 8 27 8 M5 160 112 9 264 127 4 13 8 172 276 12 5 5 17 02 0 131 42 138 275 1 18 92 129 52 26 19 60 56 158 145 8 1 0 R2 0 Dimensions of the installati...

Page 38: ...smit signal 4 Termination Termination 5 Termination Termination 6 TXD Transmit signal inverted 7 Termination Termination 8 Termination Termination Diagnostic LEDs LED Color Status Description LNK Gree...

Page 39: ...nterfaces Due to the large number of USB devices available on the market B R cannot guarantee their functionality Functionality is ensured when using the USB devices available from B R Important Becau...

Page 40: ...r repairs if the fuse is destroyed in the event of error fuse replacement Danger This device is only permitted to be supplied with protective extra low voltage PELV Protective earth grounding clip on...

Page 41: ...against electrostatic discharge on page 7 The environmental conditions must be observed When installed in a closed housing enough space must be available for air to circulate sufficiently The device...

Page 42: ...e device must ultimately be installed in a protective housing with sufficient rigidity per UL61010 1 and UL61010 2 201 4 1 2 Mounting with retaining clips Figure Retaining clip The retaining clips are...

Page 43: ...lade screw driver Tightening torque 0 4 Nm Figure Securing the retaining clips 4 1 3 Installation instructions The Power Panel must be mounted using the retaining clips included in delivery tightening...

Page 44: ...fied air circulation clearance values are based on worst case operation at the maximum spec ified ambient temperature see Temperature values in chapter Technical data If the specified air circulation...

Page 45: ...Commissioning Installation Power Panel T30 User s manual V1 42 Translation of the original documentation 45 Mounting shield attachment plate for 4 3 Power Panel...

Page 46: ...rams show the permissible mounting orientations of Power Panels The operating temperature limit values specified in the technical data apply taking into account the permissible mounting orientations T...

Page 47: ...and touch screen If functional ground is not present faults in interface communication and touch screen functionality can occur The device is only permitted to be operated if properly grounded Power P...

Page 48: ...rail in the control cabinet using a short path Securing the conductor lines to the grounding plate 1 Ground conductor The connection to ground potential must be as short as possible and sufficiently s...

Page 49: ...in any other way endangers the safety and functionality of the devices and the connected systems The operator is responsible for following all applicable safety and accident prevention regulations as...

Page 50: ...azard The USB interface if it is not permanently connected is only permitted to be used for maintenance work setup or programming in non hazardous environments Continual use in explosive atmospheres i...

Page 51: ...er Panel is held in your hands Defined touch keys The following touch keys virtual keys are predefined if the Visual Components object is used for designing the HMI application in Automation Studio VK...

Page 52: ...ce Nevertheless calibrating the device is recommended in order to achieve the best results and to adapt the touch screen to the user s preferences During the calibration process the specified point mu...

Page 53: ...t field blinking text input cursor has the focus q w e r t y u i o p a s d f g h j k l z x c v b n m 123 The 123 ABC 1 2 and 2 2 keys can be used to open additional keyboard layouts 1 2 3 4 5 6 7 8 9...

Page 54: ...ight buttons of the mouse simultaneously for at least 2 seconds if a USB mouse is connected Opened automatically after restarting the Power Panel if the corresponding Start mode is configured on servi...

Page 55: ...DHCP server Language of the service pages As can be seen in the previous service page example all of the content on the service pages for the Power Panel is generally in English Saving the settings Wh...

Page 56: ...the menu using a different background color 3 The selection list indicates the selected option Pressing the up down arrows moves between the available options 4 Checkbox not activated 5 Checkbox acti...

Page 57: ...Settings for the VNC client on Power Panel Web Settings for the web browser Storage Settings for accessing memory USB flash memory user memory Update Updates the Power Panel manual Backup Reset Backi...

Page 58: ...on that is available on a VNC server In Start mode VNC option Show boot logo is also used to configure if the system boot logo and boot animation should be displayed when establishing a connection to...

Page 59: ...in the network using this name which allows it to be accessed e g by Automation Studio Important information The hostname must be unique in the network The name can have a maximum length of 64 charact...

Page 60: ...me dns suffix The full domain name could for example look like this Hostname ppt visualization machine 01 DNS suffix network domain com Fully qualified domain name FQDN ppt visualization machine 01 ne...

Page 61: ...tion can be obtained from the network or system ad ministrator Information IP addresses are checked for validity when they are entered Only characters that build a valid IP address can be entered If t...

Page 62: ...NTP server After enabling the option one to four NTP servers can be entered Startup Network Time Screen Audio Hand button VNC Web Storage Update NTP client NTP server 1 NTP server 2 NTP server 3 NTP...

Page 63: ...splay and the basic setting for the display are configured after restarting the device Each change to a value on the service page directly and immediately affects the brightness of the display The cur...

Page 64: ...ion to the left edge of the display Boot animation top pos Default setting 0 Entry range 0 to 2048 1 Unit Pixels Function Definition of the distance from an existing boot animation to the top edge of...

Page 65: ...off Calibrate touch Start screensaver after Default setting 15 Entry range 1 to 60 Unit Minutes If there is no touch screen activity for the specified duration the screensaver is started Touching the...

Page 66: ...10 to 500ms 10 Test buzzer Press to test Buzzer source Default setting Touch screen The following options are available for triggering a buzzer Touch In VNC and Web mode an audio signal is output for...

Page 67: ...e VNC Web mode If the Hand button is pressed this information is transferred to the server configuration in Automation Studio The transfer to the server only takes place after releasing the Hand butto...

Page 68: ...lication Key codes for input field Button key code The following tables list key codes can be entered in field Button key code Information When entering the key codes it is important to ensure that th...

Page 69: ...ALT Left Alt key KEY_0 0 KEY_HOME Pos1 Home key Special characters KEY_END End key Key code Description KEY_PAGEUP Page up key KEY_ KEY_PAGEDOWN Page down key Minus KEY_UP Up cursor key KEY_ KEY_DOWN...

Page 70: ...ode Description Exclamation mark Tilde Quotation marks Accent acute Hash mark Pound symbol Dollar Yen symbol Percent Euro symbol Ampersand Plus Left parenthesis Less than Right parenthesis Greater tha...

Page 71: ...is displayed in the input field Server By default port 5900 is used to establish a connection If the VNC based HMI application is available on a different port the port number must be specified explic...

Page 72: ...ord is stored on the device as plain text Use RFB extension Default setting Disabled With the RFB extension enabled a B R VNC server VNC based HMI application can query data from the VNC client and ex...

Page 73: ...to enter multiple servers in a list Entering the hostname or IP address and then clicking on the icon adds the specified server in the list at the end of this services page see webserver1 and webserve...

Page 74: ...Keyboard on page 53 Disabled The virtual keyboard for the web page is automatically shown if a text input field in the web browser has the focus This functionality must be made available by the web se...

Page 75: ...CIFS memory location usershare Internal user memory flash on the Power Panel The USB memory must be formatted using the FAT32 file system The following image shows the default settings for service pa...

Page 76: ...Panel T30 User s manual V1 42 Translation of the original documentation Encrypt password Default setting Enabled Enabled The password is stored on the device in encrypted form Disabled The password i...

Page 77: ...nfigured update server see Configuring the update server on page 79 The following update files are searched for File type Filename PPT image PPTImage img gz PPTImage md5 see PPT image on page 90 Syste...

Page 78: ...3 The names of the listed configurations match the names of the configurations in Automation Studio If a configuration entry is selected a dialog box appears asking for installation of the configurati...

Page 79: ...on the selected update server type They are described in the following two sections 5 1 11 1 1 Configuring an TFTP update server If option Get Update Server from DHCP server is disabled and update ser...

Page 80: ...ame must be entered here FTP password Default setting EMPTY no password entered Entry range Max 100 characters To access an update server of type FTP an FTP password must be entered here The FTP passw...

Page 81: ...Exit are included when creating a backed up Settings and service pages that have not been saved are not backed up Backup settings Button Accessing this function creates a backup of the settings and s...

Page 82: ...setting EMPTY no password entered Entry range Max 100 characters The service password is used to control access to the service pages see Entering the service password on page 54 The password is store...

Page 83: ...sed as the address for the OPC UA server Important The OPC UA server is stopped while the Power Panel service page is active Port Default setting 4840 The port number used to reach the OPC UA server o...

Page 84: ...ered here Password Default setting EMPTY no password entered Entry range Max 100 characters For access with authentication a password must be entered here The password is stored in configuration file...

Page 85: ...t Security OPC UA Save Exit About Info Save changes exit Press to save changes and exit Save changes Press to save changes Exit without saving Press to exit without saving changes Save changes exit Bu...

Page 86: ...Show license Press to show license The following information about the Power Panel is displayed on this service page System time Current time System date Current date Temperature 0 Temperature of the...

Page 87: ...Automation Studio upgrade 2 Configuring the Power Panel according to requirements in Automation Studio 3 Insert a USB flash drive in your computer and select the following menu item in Automation Stu...

Page 88: ...ades Download the upgrade package in ZIP format not EXE format 2 Unzip the ZIP file with the corresponding content directly into the root directory of a USB flash drive PPTImage img gz PPTImage md5 Re...

Page 89: ...ificates in the browser If user defined certificates are required for the browser running on the Power Panel they can be provided as follows Set up network sharing for internal user memory usershare S...

Page 90: ...in Automation Studio and then the data for the USB flash drive is generated then Automation Studio will compress the boot logo into the GZ format and name the file accordingly The user only has to mak...

Page 91: ...ions remain Read the controller s operating hours Information Additional information about the RFB extensions and programming with the AsRfbExt library can be found in Automation Help Information Only...

Page 92: ...parameters The application can get the display brightness from an input field which has also been defined in the HMI application The display brightness set with dim changes the current display settin...

Page 93: ...on Serif Liberation Mono Verdana Substitute fonts font mapping If the HTML based HMI application mapp View contains fonts that do not exist on the PPT system the following system fonts are used instea...

Page 94: ...rmation Additional information about OPC UA and programming with library AsOpcUac is available in Au tomation Help Graphical OPC UA clients During development it is helpful to use a graphical OPC UA c...

Page 95: ...differ from the indices generated on the device The recommended procedure here is to dynamically determine the namespace indexes and use a namespace cache Important Attribute NodeId of each node can c...

Page 96: ...server Time MemoryAvailable Available RAM in MB MemoryTotal Entire RAM of system in MB OpenServicePage Configures opening the service page call with the Hand button Hand button PrimaryDNS Address of t...

Page 97: ...Reboots the Power Panel and start the update process 6 6 1 5 Device properties Device properties product specific information of the Power Panel is located under the following path Path 0 Root 0 Objec...

Page 98: ...ternative path function group 0 Root 0 Objects 2 DeviceSet 4 PowerPanelT30 3 Diagnostics 4 CPUCore0Usage Node attribute NodeClass Variable DataType Byte AccessLevel CurrentRead UserAccessLevel Current...

Page 99: ...on 99 6 6 2 1 4 MemoryTotal Entire RAM of system in MB Path to the node BrowsePath Path 0 Root 0 Objects 2 DeviceSet 4 PowerPanelT30 2 ParameterSet 4 MemoryTotal Alternative path function group 0 Root...

Page 100: ...1 EnableBuzzer Function identical to Service page Audio Buzzer on page 66 Path to the node BrowsePath Path 0 Root 0 Objects 2 DeviceSet 4 PowerPanelT30 2 ParameterSet 4 EnableBuzzer Alternative path f...

Page 101: ...Set 4 PowerPanelT30 3 Configuration 4 Audio 4 BuzzerFrequency Node attribute NodeClass Variable DataType UInt16 AccessLevel CurrentRead CurrentWrite UserAccessLevel CurrentRead CurrentWrite 6 6 2 2 1...

Page 102: ...Service page R W 4 OpenServicePage Configuration of the Hand button Hand button 6 6 2 2 2 1 OpenServicePage Function identical to Service page Hand button Open service page on page 67 Path to the node...

Page 103: ...Static IP address of the Power Panel Network SubnetMask Subnet mask Network 4 DefaultGateway IP address of the default gateway Network 6 6 2 2 3 1 Hostname Function identical to Service page Network...

Page 104: ...Function identical to Service page Network Get DNS from DHCP server on page 60 Path to the node BrowsePath Path 0 Root 0 Objects 2 DeviceSet 4 PowerPanelT30 2 ParameterSet 4 GetDNSFromDHCP Alternativ...

Page 105: ...ge Network Subnet mask Default gateway on page 61 Path to the node BrowsePath Path 0 Root 0 Objects 2 DeviceSet 4 PowerPanelT30 2 ParameterSet 4 SubnetMask Alternative path function group 0 Root 0 Obj...

Page 106: ...tion 4 Screen 4 DisplayBrightness Node attribute NodeClass Variable DataType Byte AccessLevel CurrentRead CurrentWrite UserAccessLevel CurrentRead CurrentWrite 6 6 2 2 4 2 ScreenRotation Function iden...

Page 107: ...n 4 ScreensaverIdleTime Node attribute NodeClass Variable DataType UInt16 AccessLevel CurrentRead CurrentWrite UserAccessLevel CurrentRead CurrentWrite 6 6 2 2 4 5 ScreensaverType Function identical t...

Page 108: ...rPanelT30 2 ParameterSet 4 StartMode Alternative path function group 0 Root 0 Objects 2 DeviceSet 4 PowerPanelT30 3 Configuration 4 Startup 4 StartMode Node attribute NodeClass Variable DataType BrSta...

Page 109: ...oryShare UserMemoryShare Function identical to Options on Service page Storage on page 75 USBMemoryShare Option Allow access to USB memory via network UserMemoryShare Option Allow access to user memor...

Page 110: ...the node BrowsePath Path 0 Root 0 Objects 2 DeviceSet 4 PowerPanelT30 2 ParameterSet 4 EnableNTPClient Alternative path function group 0 Root 0 Objects 2 DeviceSet 4 PowerPanelT30 3 Configuration 4 T...

Page 111: ...attribute NodeClass Variable Datentyp String AccessLevel CurrentRead CurrentWrite UserAccessLevel CurrentRead CurrentWrite 6 6 2 2 8 2 UseRfbExtension Function identical to Service page VNC Use RFB ex...

Page 112: ...ath 0 Root 0 Objects 2 DeviceSet 4 PowerPanelT30 2 ParameterSet 4 WebServer Alternative path function group 0 Root 0 Objects 2 DeviceSet 4 PowerPanelT30 3 Configuration 4 Web 4 WebServer Node attribut...

Page 113: ...f the device 4 StartUpdate Reboots the Power Panel and start the update process 6 6 2 3 1 AwakePanel Wakes up the Power Panel when the screensaver is running Path to the node BrowsePath Path 0 Root 0...

Page 114: ...th 0 Root 0 Objects 2 DeviceSet 4 PowerPanelT30 2 MethodSet 4 LoadConfiguration Alternative path function group 0 Root 0 Objects 2 DeviceSet 4 PowerPanelT30 3 Control 4 LoadConfiguration Arguments for...

Page 115: ...tomatic NTP time synchronization is disabled see Service page Time on page 62 Path to the node BrowsePath Path 0 Root 0 Objects 2 DeviceSet 4 PowerPanelT30 2 MethodSet 4 SetTime Alternative path funct...

Page 116: ...e 91 Path to the node BrowsePath Path 0 Root 0 Objects 2 DeviceSet 4 PowerPanelT30 2 ParameterSet 4 Temperature0 Alternative path function group 0 Root 0 Objects 2 DeviceSet 4 PowerPanelT30 3 Status 4...

Page 117: ...ys can also be read out directly via the OPC UA interface with the nodes described below see Key Bit number Path to the node BrowsePath Path 0 Root 0 Objects 2 DeviceSet 4 PowerPanelT30 2 ParameterSet...

Page 118: ...ustomized models 6 6 2 6 1 CompatibilityId ID to indicate compatibility A future version of the device could be equipped with different technology Although the module name and func tionality of the de...

Page 119: ...Manufacturer Alternative path function group 0 Root 0 Objects 2 DeviceSet 4 PowerPanelT30 2 Identification 2 Manufacturer Node attribute NodeClass Variable DataType String AccessLevel CurrentRead User...

Page 120: ...Number Serial number of the device see label on back of the device Path to the node BrowsePath Path 0 Root 0 Objects 2 DeviceSet 4 PowerPanelT30 2 SerialNumber Alternative path function group 0 Root 0...

Page 121: ...0 VendorId Vendor ID for customized models VendorId Description 0 B R 1 B R 2 Customer ID Path to the node BrowsePath Path 0 Root 0 Objects 2 DeviceSet 4 PowerPanelT30 3 VendorId Alternative path func...

Page 122: ...2 DeviceSet 4 PowerPanelT30 ns BrowseName of the information Description 2 DeviceManual Link to the website The user s manual is located in the Downloads section 6 6 2 7 1 DeviceManual Link to the we...

Page 123: ...network the following settings must be enabled in configuration DNS parameters Activate DNS service Get DNS from DHCP server In configuration OPC UA system Activate OPC UA system Configuration of the...

Page 124: ...cloth The cloth should be moistened with water and detergent a screen cleaning agent or alcohol ethanol The cleaning agent should be applied to the cloth beforehand not sprayed directly on the Power...

Page 125: ...ting time of 50 000 would mean that the display would still retain 50 of its brightness after this time How can the service life of backlights be extended Setting the display brightness to the lowest...

Page 126: ...ation How can image persistence be reduced Constantly switching between static and dynamic images Avoiding excessive brightness differences between foreground and background elements Using colors with...

Page 127: ...cable RJ45 to RJ45 2 m X20CA0E61 00300 POWERLINK connection cable RJ45 to RJ45 3 m X20CA0E61 00500 POWERLINK connection cable RJ45 to RJ45 5 m X20CA0E61 00800 POWERLINK connection cable RJ45 to RJ45...

Page 128: ...10 01 0TB6102 2110 01 Terminal block Number of pins 2 female Type of terminal block Screw clamp terminal block Cage clamp terminal block Cable type Only copper wires no aluminum wires Spacing 3 81 mm...

Page 129: ...ce description in section Technical data for the individual products On the website www br automation com in section Technical data for the individual products possible to search using model number On...

Page 130: ...industrial use Applicable standards from this directive EN 61131 2 Programmable logic controllers Part 2 Guidance for inspection and routine testing EN 61000 6 2 Electromagnetic compatibility EMC Part...

Page 131: ...declaration of conformity Declaration of conformity PDF Website Downloads Certificates Declarations of conformity Declaration of conformity ATEX Power Panel T30 Certificate type approval certificate P...

Page 132: ...cation of groups of environmental parameters and their severities Section 2 Transport EN 60721 3 3 Classification of environmental conditions Part 3 Classification of groups of environmental parameter...

Page 133: ...nue to operate as intended Temporary degradation of performance must be self recover able C Loss of functions accepted but no destruction of hardware or software program or data The PLC system shall c...

Page 134: ...150 kHz to 80 MHz 80 AM 1 kHz Criteria A 1 Only for connections with a permitted line length greater than 3 m Magnetic fields with electrical frequencies Testing performed per standard EN 61000 4 8 R...

Page 135: ...N 55016 2 1 Limit values per standard EN 61131 2 Zone B Limit values per standard EN 61000 6 4 150 to 500 kHz 79 dB V quasi peak value 66 dB V average value AC mains connection 150 kHz to 30 MHz 500 k...

Page 136: ...s in all 3 axes x y z 1 octave per minute Vibration sinusoidal Transport packaged Testing performed per stan dard EN 60068 2 6 Requirements per standard EN 60721 3 2 Class 2M1 Requirements per standar...

Page 137: ...dangerous parts with fingers Back IP20 Second number IPx0 Not protected Requirement per manufacturer Explanation of code num bers per standard EN 60529 Meaning for the protection of equipment Meaning...

Page 138: ...time certificates type approval are generally accepted by other classi fication societies during ship acceptance procedures For corresponding environmental categories see the technical data for the re...

Page 139: ...Publishing information Power Panel T30 User s manual V1 42 Translation of the original documentation 139...

Page 140: ...Panel T30 User s manual V1 42 Translation of the original documentation Publishing information B R Industrial Automation GmbH B R Strasse 1 5142 Eggelsberg Austria Telephone 43 7748 6586 0 Fax 43 7748...

Reviews: