Commissioning • Installation
44
Power Panel T30 User's manual V1.42 - Translation of the original documentation
Air circulation - Side view
Air outlet
>60 mm
>60 mm
>45 mm
Air intake
Information:
The specified air circulation clearance values are based on worst-case operation at the maximum spec-
ified ambient temperature (see "Temperature values" in chapter "Technical data").
If the specified air circulation clearance values cannot be observed, then the internal housing temper-
ature must be monitored by the user and appropriate measures taken if they are exceeded (see
perature monitoring" on page 91
).