METHOD FOR ADJUSTMENT OF PID PARAMETERS

In order to setup values for start-up on PID, we recommend to use the Ziegler-Nichols open loop method.

Proceed as follows:

- Connect a recorder to the analogue output or write the displayed values, then draw the diagram pH vs. time.
- Switch on MANUAL the PID regulation mode.
- Reach and keep the measurement close to the set point by adjusting the PID output.

- Apply a step (∆Cde) of 10 % for instance, on the analogue output (e.g. If preset value was 30%, apply 40%).
- Note on the diagram the corresponding time for this event (step of +10%).
- Find out on this diagram both times t and T:

t = delay of response
T = Time corresponding to a variation Δm of measurement equal to percentage of variation
∆Cde of output (∆m = ∆Cde)
This value may be found out from the slope at the beginning of measurements.

- Set up the PID parameters with the values from the following table:

Regulation

Gain

Ti [s]

Td [s]

PID

1,2 x T/t

2 x t

0,5 x t

PI

0,9 x T/t

3,3 x t

00

P

T/t

9999

00

PID

analogue

output

8.4

In MANUAL mode (REGUL. MANU)

pH measurement

Reached set point

Time

Time

∆Cde = 10 %

∆m = 10 %

To

To

9.10 TYPE OF INSTRUMENT

pH / RH CHOICE

Choose your application, then confirm
pH - METER for pH monitoring
RH - METER for ORP applications

SAVE ?

To record the settings, press the icon SAVE.

9.11 FORCED MEASURE

It is possible to force the measurement or the PID.

The first line shows the current measurement.
Confirm to access to the keyboard.
Enter the value you need to simulate.

Note: The value is immediately considered by BAMOPHAR (thresholds, regulation, 4-20mA outputs ...)

To exit this menu, press icon RETURN KEY.

Note : It is possible to force the output 4-20 mA for PID when PID regulation is in manual mode (REGUL. MANU).
If PID regulation is operating, the display of analogue output is in %.

MES

23-11-2018

M-107.01-EN-AE

107-01

/15

pH/ mV monitors

BAMOPHAR 107

22, Rue de la Voie des Bans · Z.I. de la gare · 95100 ARGENTEUIL

Tel

Fax

+33 (0)1 30 25 83 20

+33 (0)1 34 10 16 05

Web

E-mail

www.bamo.eu

[email protected]

INTERNATIONAL

Summary of Contents for BAMOPHAR 107

Page 1: ...MANUAL MES 23 11 2018 M 107 01 EN AE 107 01 1 pH mV monitors BAMOPHAR 107 22 Rue de la Voie des Bans Z I de la gare 95100 ARGENTEUIL Tel Fax 33 0 1 30 25 83 20 33 0 1 34 10 16 05 Web E mail www bamo...

Page 2: ...RELAY OUTPUTS S1 S2 AND S3 AS THRESHOLDS 9 2 1 11 COMMENTS ABOUT REGULATION WITH BAMOPHAR 9 2 2 11 ADJUSTMENT OF THRESHOLDS S1 S2 AND S3 IN MODE ON OFF REGULATION 9 2 3 11 ASSIGNMENT OF S3 THRESHOLD...

Page 3: ...sensor or cleaning mode Contact Initial resistance 100 m max voltage drop 6 V DC 1 A Switching power 831 VA AC 3 A 277 V AC 90 W 3 A 30 V DC Switching capacity min 100 mA 5 V DC depending of frequency...

Page 4: ...top cover Measurement input Screw connector for pH cable type 9060 Note Signal input on screw connector for 9060 cable type Only for wall mount models codes 107520 107521 107523 and 107524 MES 23 11...

Page 5: ...O contact for measurement temperature 21 S1 22 Relay S3 N O contact for measurement or temperature 23 S3 May be assigned to the external signal becomes NC contact see 9 2 3 24 25 Main power supply 26...

Page 6: ...ayed as pH 7 4 3 1 9060 coaxial cable preparation 1 4 2 5 6 3 Remove the outer insulation by 20 mm Fold back the shield copper mesh Remove the 2nd sheath black layer over 20 mm Strip the core of the c...

Page 7: ...ontact between the copper shield and the 2 brackets will be perfect 6 Press on the cable to insert it properly in the brackets 7 Screw on tightly to block the tip in its connector 8 Replace the lid of...

Page 8: ...tatus of relays S1 S2 S3 S4 Designations Identifications of your instruments Measurements display Parameter settings of both BAMOPHAR Display settings Date and time Measurements details Opened or clos...

Page 9: ...Confirm setting and go to the next parameter SAVE To save the parameters Closed means CONSULTATION review mode e g Green icon for extension unit 7 DISPLAY SETTINGS Note To access to the display setti...

Page 10: ...buffer pH 4 00 for a process with acids Press MENU and choose ADJUST ELECTRODE STANDARD 7 00 pH Plunge the tip of the electrode in the pH 7 00 buffer solution Ref 9011 then confirm Do not forget to re...

Page 11: ...e the relay S1 select OFF mode then confirm and save the setting ALARM 1 MEASURE TEMP In ON mode threshold S1 can be set in MEASUREMENT or TEMPERATURE mode MEASURE mode threshold dedicated to pH or mV...

Page 12: ...UT 4 20 mA or 0 20 mA Select the right scale 4 20 mA or 0 20 mA for output signal then confirm SAVE To record the settings press the icon SAVE 9 5 SETTINGS OF ANALOGUE OUTPUT FOR TEMPERATURE Go to men...

Page 13: ...tings press the icon SAVE Cycle time High limit Set point Low limit Time S1 actuated No action Dead zone Measurement S2 EXAMPLE For settings such as following Set point pH 7 00 Cycle time 10 s Upper b...

Page 14: ...o go to ADJUST ALARM To access to the CLEANING PROBE menu switch alarms mode to WITHOUT ALARM in menu ADJUST ALARM If the ALARM mode is not activated the CLEANING PROBE function is available CLEANING...

Page 15: ...Ti s Td s PID 1 2 x T t 2 x t 0 5 x t PI 0 9 x T t 3 3 x t 00 P T t 9999 00 PID analogue output 8 4 In MANUAL mode REGUL MANU pH measurement Reached set point Time Time Cde 10 m 10 To To 9 10 TYPE OF...

Reviews: