9.8

OUTPUT S4 SETTINGS

9.8.1 DEFAULT SETTING

By default, relay S4 is dedicated to alarms on pH and temperature faults:

- The contact closes, if the measurement is less than pH 0.10
- The contact closes if the measurement is above pH 14.10.
- The contact closes if the sensor Pt 100 is faulty (damaged cable).

Otherwise, relay S4 can be dedicated to another function:
• Either in alarm (relay fault S1 or S2): See § ADJUST ALARM
• Or cleaning function: See § CLEANING PROBE

9.8.2 ADJUST ALARM

This function activates relay S4 when the switch-on time of relays S1 or S2 is too long (e.g. injection time too long).

Go to the menu ADJUST ALARM

• This ALARM function is not available if the CLEANING PROBE mode is activated; So, go to:

CLEANING PROBE MODE

Deactivate first the cleaning function in CLEANING PROBE menu before to access to ADJUST
ALARM menu..

• If the CLEANING PROBE mode is disabled, the ADJUST ALARM function is available:

WITH ALARM / WITHOUT ALARM

Select WITH ALARM to activate the relay S4, then confirm.

TIME S1 0005 Sec

Enter the holding time max. for relay S1, then confirm.

TIME S2 0020 Sec

Enter the holding time max. for relay S2, then confirm.

SAVE ?

To record the settings, press the icon SAVE.

9.8.3 CLEANING PROBE

This function actuates the S4 relay when automatic cleaning of the electrode is required.
In order not to disturb the regulation, measurements are frozen during the cleaning routine.

Go to the menu CLEANING PROBE.

• If alarms are set up in ADJUST ALARM, the cleaning mode menu is not available; So, go to:

ADJUST ALARM

To access to the CLEANING PROBE menu, switch alarms mode to WITHOUT ALARM in menu

ADJUST ALARM.

• If the ALARM mode is not activated, the CLEANING PROBE function is available.

CLEANING YES / NO

Select YES to set up the cleaning routine, then confirm.

PERIOD 2300 Sec

Enter the cycle time between two cleaning routines, then confirm.

TIME 0010 Sec

Enter the duration of cleaning routine, then confirm.

DELAY 0010 Sec

Enter the delay before the measurement is resumed.

SAVE ?

To record the settings, press the icon SAVE.

9.9

PID REGULATION

REGUL. PID allows seting of a PID regulation through analogue output (0...20 or 4...20 mA) between terminals 3 and 4.

This output is no more dedicated to the copy of temperature measurement.

Go to the menu REGUL. PID

REGULATION ON / OFF

Select ON to set up the function PID REGULATION, then confirm.

REGUL. AUTO / MANU

Select AUTO to access to parameters, then confirm.

SET VAL 07.00 pH

Enter the value of desired trigger point, then confirm.

GAIN : 4.800

Enter the required proportional gain value, then confirm.

Ti : 0050 Sec

Enter the value for integral timer, then confirm.

Td : 0012 Sec

Enter the required value for derivative timer, then confirm.

ACID INJECTION / BASE INJECTION

Select the right chemical, then confirm.

OUTPUT 4/20 mA or 0/20 mA

Select the required output signal range, then confirm.

SAVE ?

To record the settings, press the icon SAVE.

Note: To block the PID regulation, set a voltage of 24V DC (=20 mA)between terminals 5 (+) and 6 (0).

MES

23-11-2018

M-107.01-EN-AE

107-01

/14

pH/ mV monitors

BAMOPHAR 107

22, Rue de la Voie des Bans · Z.I. de la gare · 95100 ARGENTEUIL

Tel

Fax

+33 (0)1 30 25 83 20

+33 (0)1 34 10 16 05

Web

E-mail

www.bamo.eu

[email protected]

INTERNATIONAL

Summary of Contents for BAMOPHAR 107

Page 1: ...MANUAL MES 23 11 2018 M 107 01 EN AE 107 01 1 pH mV monitors BAMOPHAR 107 22 Rue de la Voie des Bans Z I de la gare 95100 ARGENTEUIL Tel Fax 33 0 1 30 25 83 20 33 0 1 34 10 16 05 Web E mail www bamo...

Page 2: ...RELAY OUTPUTS S1 S2 AND S3 AS THRESHOLDS 9 2 1 11 COMMENTS ABOUT REGULATION WITH BAMOPHAR 9 2 2 11 ADJUSTMENT OF THRESHOLDS S1 S2 AND S3 IN MODE ON OFF REGULATION 9 2 3 11 ASSIGNMENT OF S3 THRESHOLD...

Page 3: ...sensor or cleaning mode Contact Initial resistance 100 m max voltage drop 6 V DC 1 A Switching power 831 VA AC 3 A 277 V AC 90 W 3 A 30 V DC Switching capacity min 100 mA 5 V DC depending of frequency...

Page 4: ...top cover Measurement input Screw connector for pH cable type 9060 Note Signal input on screw connector for 9060 cable type Only for wall mount models codes 107520 107521 107523 and 107524 MES 23 11...

Page 5: ...O contact for measurement temperature 21 S1 22 Relay S3 N O contact for measurement or temperature 23 S3 May be assigned to the external signal becomes NC contact see 9 2 3 24 25 Main power supply 26...

Page 6: ...ayed as pH 7 4 3 1 9060 coaxial cable preparation 1 4 2 5 6 3 Remove the outer insulation by 20 mm Fold back the shield copper mesh Remove the 2nd sheath black layer over 20 mm Strip the core of the c...

Page 7: ...ontact between the copper shield and the 2 brackets will be perfect 6 Press on the cable to insert it properly in the brackets 7 Screw on tightly to block the tip in its connector 8 Replace the lid of...

Page 8: ...tatus of relays S1 S2 S3 S4 Designations Identifications of your instruments Measurements display Parameter settings of both BAMOPHAR Display settings Date and time Measurements details Opened or clos...

Page 9: ...Confirm setting and go to the next parameter SAVE To save the parameters Closed means CONSULTATION review mode e g Green icon for extension unit 7 DISPLAY SETTINGS Note To access to the display setti...

Page 10: ...buffer pH 4 00 for a process with acids Press MENU and choose ADJUST ELECTRODE STANDARD 7 00 pH Plunge the tip of the electrode in the pH 7 00 buffer solution Ref 9011 then confirm Do not forget to re...

Page 11: ...e the relay S1 select OFF mode then confirm and save the setting ALARM 1 MEASURE TEMP In ON mode threshold S1 can be set in MEASUREMENT or TEMPERATURE mode MEASURE mode threshold dedicated to pH or mV...

Page 12: ...UT 4 20 mA or 0 20 mA Select the right scale 4 20 mA or 0 20 mA for output signal then confirm SAVE To record the settings press the icon SAVE 9 5 SETTINGS OF ANALOGUE OUTPUT FOR TEMPERATURE Go to men...

Page 13: ...tings press the icon SAVE Cycle time High limit Set point Low limit Time S1 actuated No action Dead zone Measurement S2 EXAMPLE For settings such as following Set point pH 7 00 Cycle time 10 s Upper b...

Page 14: ...o go to ADJUST ALARM To access to the CLEANING PROBE menu switch alarms mode to WITHOUT ALARM in menu ADJUST ALARM If the ALARM mode is not activated the CLEANING PROBE function is available CLEANING...

Page 15: ...Ti s Td s PID 1 2 x T t 2 x t 0 5 x t PI 0 9 x T t 3 3 x t 00 P T t 9999 00 PID analogue output 8 4 In MANUAL mode REGUL MANU pH measurement Reached set point Time Time Cde 10 m 10 To To 9 10 TYPE OF...