12 / 36
0006081428_201406
ENGLISH
PIPELINE SIZE TABLE TBML 160 PN
GRAVITY SUPPLY SYSTEM
1 Tank
2 Feeding pipe
3 Wire-net filter
4 Pump
5 Degasifier
6 Suction pipe
7 Return pipe
8 Automatic fuel interception at burner shut off
9 One-way valve
SIPHON FEED SYSTEM WITH FEED FROM THE TOP OF THE TANK
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
8 Automatic fuel interception device at
burner shut off
9 One-way valve
10 Bottom valve
SUCTION FEED SYSTEM
Note:
For any missing devices in the piping, follow existing regulations.
H = Difference in level between level in the tank and the pump axis.
L = Maximum length of suction pipe including the vertical lift. Subtract 0.25 mt.
for every bend or gate valve.
Dimension P = 3.5 m. (max.)
PUMP AXIS
PUMP AXIS
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
10 Bottom valve
PUMP AXIS
H
Total length
metres
metres
Ø i. 16 mm.
1 40
1.5
45
2
45
2.5
50
3
50
H
Total length
metres
metres
Ø i. 16 mm.
1 40
1.5
45
2
45
2.5
50
3
50
H
meters
Total length meters
Ø i. 14 mm.
Ø i. 16 mm.
0,5
36
55
1
30
48
1,5
25
41
2
20
32
2,5
15
24
3
10
15
3,5
4
7,5