ENGLISH
30 / 38
0006081053_201805
MAINTENANCE
Analyse combustion gases and check that the emission values
are correct at least once a year, in compliance with current law.
• Clean air dampers, the air pressure switch with pressure port
and the relevant pipe, if any.
• Check the electrode condition. Replace them, if necessary.
• Clean the photocell. Replace it, if necessary.
•
Have the burner and the chimney cleaned by specialised
personnel (stove repairer); a clean burner is more efficient, lasts
longer and is quieter.
•
Check that the fuel filter is clean. Replace it, if necessary.
•
Check that all components of the combustion head are in good
condition, have not been deformed and are free from deposits
deriving from the installation environment and/or from poor
combustion.
•
Analyse combustion gases and check emissions values.
If it is necessary to clean the outside of the combustion head, take
out its components according to the procedure described:
•
Disconnect the diesel hoses (24) from the connectors beneath
the head unit (mind the dripping).
•
Undo the two screws (11) and turn the burner around the pin
(10) inside the specific hinge (figure 1).
•
After pulling out the ignition cables (14) from the relating
electrodes, undo completely the locking nuts (6) from mixing
unit.
•
Lift up the mixing unit (18) until the pipes come out and then
pull the mixing unit out completely in the direction indicated by
the arrow.
• Complete the maintenance operations, proceed with the
assembly of the mixing unit by carrying out the above operations
in reverse order, after checking that the ignition electrodes and
the flame disk are correctly positioned.
DANGER / ATTENTION
When closing the burner, gently pull the two ignition cables
towards the electrical panel, putting them slightly in tension,
then arrange them in their housing on the scroll. This will
ensure that the two cables do not get damaged by the fan
during burner operation.
10
11
24
0002935140
Fig.1
6
14
0002935150
18
0002935160
0002935170
Summary of Contents for TBL 210P
Page 2: ......
Page 38: ...ITALIANO 36 38 0006081053_201805 SCHEMI ELETTRICI...
Page 39: ...ITALIANO 37 38 0006081053_201805...
Page 76: ...ENGLISH 36 38 0006081053_201805 WIRING DIAGRAMS...
Page 77: ...ENGLISH 37 38 0006081053_201805...
Page 79: ......