CONNECTING THE BURNER TO THE
LIQUID FUEL SUPPLY LINE
SUPPLY LINE
The fuel supply pressure to the burner pump must not change
both with burner off and with working burner at the maximum fuel
output required by the boiler.
The supply circuit can be realized without pressure regulator,
using the dedicated hydraulic diagram.
The burner tank connection pipes must be perfectly airtight. It is
recommended to use copper or steel pipes of a suitable diameter.
The pipe dimensioning must be carried out according to the pipe
length and the flow rate of the installed pump.
These instructions ensure a good operation of the product.
At the end of the rigid pipes, fuel shut-off gate valves must be
installed.
Install the filter on the suction piping after the gate, then connect
the hose to the burner pump's suction coupling nipple; all parts are
supplied with the burner.
The pump is provided with specific connections to fit control
instruments (pressure gauge and vacuum gauge).
For a safe and silent operation, the suction vacuum cannot exceed
35 cm/Hg corresponding to 0.46 bar.
The anti-pollution prescriptions, as well as the provisions set forth
by the local authorities, refer to the specific publications in force in
the country where the product will be installed.
Maximum suction and return pressure = 1 bar.