ENGLISH
15 / 38
0006081053_201805
TBL 130 - 160 - 210
GRAVITY SUPPLY SYSTEM
1
2
5
9
8
3
6
4
H
7
0002900740N1
1
Serbatoio
2
Feeding pipe
3
Mesh filter
4 Pompa
5
Degasificatore
6
Suction pipe
7
Burner return pipe
8
Automatic shut-off device with
burner off
9
Unidirectional valve
H
Total L.
Meters
Meters
Øi 16 mm
1
40
1,5
45
2
45
2,5
50
3
50
SIPHON FEED SYSTEM WITH FEED FROM THE TOP OF THE TANK
7
9
8
4
H
P
6
10
3
1
0002900740N2
Value P = 3.5 m (Max)
1
Serbatoio
3
Mesh filter
4 Pompa
6
Suction pipe
7
Return pipe
8
Automatic shut-off device with
burner off
9
Unidirectional valve
10 Foot valve
H
Total L.
Meters
Meters
Øi 16 mm
1
40
1,5
45
2
45
2,5
50
3
50
INTAKE SUPPLY SYSTEM
3
7
10
4
H
6
1
0002900740N3
1
Serbatoio
3
Mesh filter
4 Pompa
6
Suction pipe
7
Return pipe
10 Foot valve
H
Total L.
Meters
Meters
Øi 14 mm
Øi 16 mm
0,5
36
55
1
30
48
1,5
25
41
2
20
32
2,5
15
24
3
10
15
3,5
4
7,5
N.B. Comply with the regulations in force for any components missing in the
pipelines.
H = Difference in level between minimum level in tank and pump axis
L = Deduct 0.25 m for each elbow or gate.