TECHNICAL SPECIFICATIONS
MODEL
TBG 45 P
TBG 60 P
Maximum natural gas heat power
kW
450
600
Minimum natural gas heat power
kW
100
120
¹) natural gas emissions
mg/kWh
Class 3
Class 3
Operation
Two-stage
Two-stage
50 Hz natural gas transformer
26 kV - 40 mA - 230/240 V
26 kV - 40 mA - 230/240 V
Methane maximum flow rate
Stm³/h
48
63.5
Methane minimum flow rate
Stm³/h
11
12.7
Maximum natural gas pressure
hPa (mbar)
360
360
Minimum natural gas pressure
hPa (mbar)
12
20
Maximum propane thermal power
kW
450
600
Minimum propane thermal power
kW
100
120
Propane maximum flow rate
Stm³/h
18
24.5
Propane minimum flow rate
Stm³/h
4
4.9
Maximum propane pressure
hPa (mbar)
360
360
Minimum propane pressure
hPa (mbar)
30
29
²)propane emissions
mg/kWh
Class 3
Class 3
50hz fan motor rpm
r.p.m.
2730
2800
50Hz three-phase electrical data
-
3L - 400V - 1,8A - 0,9kW
50Hz single-phase electrical data
1N - 230V - 4,32A - 0,994kW
1N - 230V - 0,36A - 0,083kW
Protection rating
IP 40
IP 40
Flame detection
IONISATION PROBE
IONISATION PROBE
Control box
LME22..
LME22..
Air flow rate regulation
electric servomotor
electric servomotor
Operating ambient air temperature
°C
-15 ÷ +40
-15 ÷ +40
Sound pressure**
dBA
76
76
Sound power***
dBA
88
88
Weight with packaging
kg
40
42
Weight without packaging
kg
32
34
Calorific power below reference conditions 15° C, 1013 hPa (mbar):
Natural gas: Hi = 9,45 kWh/Stm³ = 34,02 MJ/Stm³
Propane: Hi = 24,44 kWh/Stm³ = 88,00 MJ/Stm³
For different types of gases and pressure values, contact our sales departments.
Minimum gas pressure, depending on the type of gas train used for obtaining max. flow rate with null pressure in the combustion chamber.
The measurements have been carried out in accordance with EN 15036 - 1 standard.
** The acoustic pressure measured with burner operating at maximum rated thermal output refers to the manufacturer's laboratory environment
conditions and cannot be compared to measurements carried out in different locations. Measurement accuracy σ = +/- 1.5 dB(A).
*** Acoustic pressure was obtained characterizing the manufacturer's laboratory with a sample source; this measurement has a class 2
accuracy (engineering class) with a standard deviation of 1.5 dB(A).
Propane / natural gas CO emissions ≤ 100 mg/kWh
¹) NATURAL GAS EMISSIONS
Classes defined according to EN 676 standards.
Class
NOx emissions in mg/kWh natural gas
1
≤ 170
2
≤ 120
3
≤ 80
4
≤ 60
²) PROPANE GAS EMISSIONS
Classes defined according to EN 676 standards.
Class
NOx emissions in mg/kWh propane gas
1
≤ 230
2
≤ 180
3
≤ 140
4
≤ 110
6 / 34
0006160178_202211
ENGLISH
Summary of Contents for TBG 45 P
Page 2: ......
Page 33: ...SCHEMI ELETTRICI 31 34 0006160178_202211 ITALIANO...
Page 34: ...32 34 0006160178_202211 ITALIANO...
Page 36: ...34 34 0006160178_202211 ITALIANO...
Page 67: ...WIRING DIAGRAMS 31 34 0006160178_202211 ENGLISH...
Page 68: ...32 34 0006160178_202211 ENGLISH...
Page 70: ...34 34 0006160178_202211 ENGLISH...
Page 71: ......