CONTROL AND COMMAND EQUIPMENT LMO...
OPERATION.
The reset button «EK...» is the main element to access all diagnostics functions (activa
-
tion and deactivation) and serves to unlock the command and control device.
The multi-coloured «LED» indicates the command and control device status during both
operation and diagnostics functions.
RED
YELLOW
GREEN
Both «LED» and «EK...» are positioned under the transparent button. Pressing this button, you reset the command and control equipment.
There are two diagnostics choices:
1. Visual indication directly on the reset button: operation and diagnostics of device status.
2. Diagnostics with interface: in this case the OCI400 connecting cable is necessary and it can be connected to a PC with ACS400 software, or
to gas analysers of different manufacturers.
VISUAL INDICATION.
During operation, the command and control equipment phase is indicated on the reset button. The table lists all colour sequences and their
meaning. To activate the diagnostics function, hold the reset button down for at least 3 seconds. A quick red flashing indicates that the function
is active. Likewise, hold the reset button down for at least 3 seconds to deactivate the function (the switching will be indicated with a flashing
yellow light).
EK
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
> 3 s
7101z03e0305
Operating position
PC interface / diagnostic
analyser
Colour code table
Diagnostics
Operating position
Condition
Colour sequence
Colours
Waiting time, other intermediate conditions
. . . . . . . .
No light
Fuel oil preheating "ON", max waiting time 5 s. (tw)
. . . . . . . . . Fixed
Yellow continuous
Ignition phase
Intermittent yellow
Correct operation, current strength of flame detector above the
minimum allowed
Green
Incorrect operation, current strength of flame detector below the
minimum allowed value
Intermittent green
Decrease in power supply voltage
Alternating Yellow and Red
Burner shut down condition
Red
Fault indication (see colour key)
Intermittent red
Extraneous light upon burner start-up
Alternating Green and Red
Quick flashing for diagnostics
Quick flashing red
NO LIGHT.
RED. YELLOW.
GREEN.
22 / 30
0006080890_202211
ENGLISH
Summary of Contents for BTL 14P
Page 2: ......
Page 30: ...SCHEMI ELETTRICI 28 30 0006081308_202211 ITALIANO...
Page 32: ...30 30 0006081308_202211 ITALIANO...
Page 61: ...WIRING DIAGRAMS 29 30 0006080890_202211 ENGLISH...
Page 63: ......