Installing the Drive 3-1
MN762
Chapter 3
Installing the Drive
This chapter provides information that must be considered when planning a VS1MX drive installation and provides drive
mounting information and installation site requirements.
3.1 Receiving & Inspection
When you receive your control, there are several things you should do immediately.
1. Observe the condition of the shipping container and report any damage immediately to the commercial carrier that
delivered your control.
2. Remove the control from the shipping container and remove all packing materials from the control. The container and
packing materials may be retained for future shipment.
3. Verify that the part number of the control you received is the same as the part number listed on your purchase order.
4. Inspect the control for external physical damage that may have been sustained during shipment and report any damage
immediately to the commercial carrier that delivered your control.
5. If the control is to be stored for several weeks before use, make sure that it is stored in a location that conforms to
published storage humidity and temperature specifications stated in this manual.
3.2 General Requirements for the Installation Site
It is important to ensure that the drive’s environment and operating conditions are satisfactory. The area behind the drive
must be kept clear of all control and power wiring. Power connections may create electromagnetic fields that may interfere
with control wiring or components when run in close proximity to the drive. Read the recommendations in the following
sections before continuing with the drive installation.
3.2.1 Operating Conditions
• Operating ambient temperature must be within 14°F (-10°C) to 104°F (40°C).
If ambient exceeds 40°C, de-rate the output by 5% per °C above 40°C up to 55°C maximum ambient temperature.
• Protect the cooling fan by avoiding dust or metallic particles.
• Do not expose the drive to a corrosive atmosphere.
• Protect the drive from moisture and direct sunlight.
• Verify that the drive location will meet the environmental conditions specified in Table 3-1.
• For indoor use only
3.2.2 Minimum Mounting Clearances
Be sure to provide proper top and bottom clearance 5.9 inches (150mm) for cooling.
Side to side clearance is minimal and controls can be almost touching.
Table 3-1 Ambient Temperatures and Mounting Clearances
Ambient Temperature
Enclosure Rating
Minimum Mounting Clearances
(Vertical)
Minimum
Maximum
14°F (-10°C)
104°F (40°C)
NEMA 4X / IP66
5.9 in (150mm)
104°F (40°C)
NEMA 12 / IP55
5.9 in (150mm)
3.3 Mounting the Drive
Mount the drive upright on a flat, vertical, level surface using Figure 3-2 or 3-3 for mounting hole locations.
3.3.1 Protecting the Drive from Debris
The drive is designed to operate in NEMA 12 (IP55) and NEMA 4X (IP66) Type installations. (For Indoor Use Only.)
3.3.2 Watts Loss Data
Refer to Table 2-1 for watts loss data.
3.3.3 Elevation
Maximum elevation is 3300 ft (1000m) above sea level without de-rating. De-rate output power by 1% per 330 ft (100m)
about 3300 ft to 6600 ft (2000m) maximum elevation.