Control Wiring 5-1
MN762
Chapter 5
Control Wiring
5.1 Control Board Connections
Analog and Digital input and output connections are made at the Control Wiring Terminals shown in Figure 5-1.
Control wire connections can be made using shielded twisted pair #18 AWG (0.8mm2) wire minimum. The cable must also
have an overall shield and not exceed 100 feet (30m) in length. Control wire cables must be separated from power wiring.
Separate parallel runs of control cables and power cables by at least 3”. Cross power wires at right angles only. Insulate or
tape ungrounded end of shields to prevent contact with other conductors or ground.
Figure 5-1 Control Terminals
Red
Blu
Yel
Grn
Wht Blk
Front
Panel
Potentiometer
Front
Panel
FWD-O-REV
Switch
Control Wiring
Terminals
Only on
Switched
version
Table 5-1 Control Terminal Descriptions
Terminal
Signal Description
1
+24VDC (@ 100 mA)
2
Digital In1 (8 - 30VDC)
3
Digital In2 (8 - 30VDC)
4
Digital In3 (8 - 30VDC) / Analog In2 (0 -10VDC, 0 - 20mA or 4 - 20mA)
5
+10VDC (@ 10mA) Reference for Potentiometer (1kohm minimum)
6
Analog In1 (0 -10VDC, 0 - 20mA or 4 - 20mA) / Digital In4 (8 - 30VDC)
7
Common (terminals 7 & 9 are connected)
8
Analog Output (0-10VDC @ 20mA max) / Digital Output (0-24VDC)
9
Common (terminals 7 & 9 are connected)
10
Relay Common
11
Relay N.O. Contact (rated 250VAC@6A; 30VDC@5A)