8-4 Customizing Your Application
MN762
8.2.2 Keypad Mode (P-07 = 1 or 2)
Table 8-2 Parameter P-08 Control of Digital Inputs when P-07=1 or 2
P-08
Digital In 1 (Term. 2)
Digital In 2 (Term. 3)
Digital In 3 (Term. 4)
Analog In 1 (Term. 6)
0, 1, 5,
8-12
Open
Stop
Open
KeypadSpeedRef
Open KeypadSpeed Ref
Open
Forward
Closed
Run
Closed
Remote Up*
Closed
Remote Down*
Closed
Reverse
2
Open
Stop
Open
KeypadSpeedRef
Open
KeypadSpeedRef
Open
KeypadSpeedRef
Closed
Run
Closed
Remote Up*
Closed
Remote Down*
Closed
Preset Speed 1
3*
Open
Stop
Open
KeypadSpeedRef
Open
Trip (Ext Trip)
Open
KeypadSpeedRef
Closed
Run
Closed
Remote Up*
Closed
Run
Closed
Remote Down
4
Open
Stop
Open
KeypadSpeedRef
Open
KeypadSpeedRef
Analog Input 1
Closed
Run
Closed
Remote Up*
Closed
Analog Input 1
6*
Open
Stop
Open
FWD Run
Open
Trip (Ext Trip)
Open
Keypad Speed
Ref
Closed
Run
Closed
REV Run
Closed
Run
Closed
Preset Speed 1
7*
Open
FWD Stop
Open
REV Stop
Open
Trip (Ext Trip)
Open
KeypadSpeedRef
Closed
FWD Run Closed
REV Run
Closed
Run
Closed
Preset Speed 1
*Remote Up and Remote Down are MOP (E-Pot) controls. These provide Speed Increase and Decrease inputs to allow MOP
operation. (Keypad controls remain active)
P-08 = 3, 6 or 7 Note: Connect external PTC Motor Thermistor or similar user contact to Digital Input 3.
P-08 = 7 Note: Closing both Digital Input 1 and 2 = Fast Stop (P33).
Figure 8-2 Keypad Mode Example Wiring
1
2
3
4
5
6
7
K Ohms
Keypad mode P07 = 1 or 2, P08 = 0
Note: When P-07 = 1 or 2 and P-08 = 3, 6, 0r 7
Motor Thermistor & E-Trip Connection
+24V Output
O: Stop (disable)
C: Run (enable)
C: Remote Up
C: Remote Down
+10V Output
O: Forward
C: Reverse
0V
1 +24V Output
4 Digital Input 3
Suitable for PTC Motor Thermistors
of type PT100 or similar.
Trip - Run
Trip Level set at 2.5
Only operational using E-trip terminal
function on Digital Input 3