4-2 Troubleshooting
In the event of a fault trip, the display will show the fault code
and the STATUS indicator will begin to blink red. Pressing the
UP Arrow before the fault is reset will display the status of the
drive at the time of the fault. More than one display symbol may
be shown to better define the cause of the fault.
Faults can be reset by the following methods:
1)
Pressing the Keypad STOP Key
2)
Simultaneously closing the FWD and REV terminals at the
Control Terminal Strip
3)
Removing AC Line Power
4)
By the Auto Restart feature
The following table lists the available Fault Codes. Please note
that only faults F11 through F20 will be reset by the Auto Restart
feature.
Fault Codes
Fault Code
Description
F01
Computer Malfunction
F02
Parameter Block Fault
F03
Bus Current Measurement Fault
F04
Power Supply Overload
F05
No DC Bus Voltage
F06
Output Short Circuit
F07
External Trip Fault
F10
Auto Restart Fault
F11
Ground Fault
F13
DC Bus Overvoltage
F16
Overcurrent During Acceleration
F17
Overcurrent During Deceleration
F18
Overcurrent While Running
F19
Heatsink Overtemperature
F20
Timed Overload