Operation 3-25
Parameter 82-Start Options - Continued
Value
Description
4
Manual Restart. If parameter 21-OPERATING MODE = 2, 3, or 6
(2-Wire Control) Then Run FWD or REV commands must be
removed and then re-applied to start after application of line power.
5
Auto Restart is active after application of line power and Run
Command is given at the Control Terminal Strip.
6
Synchro Start and Manual Restart
7
Synchro Start and Auto Restart
8
Manual Restart. If parameter 21-OPERATING MODE = 2, 3, or 6
(2-Wire Control) Then Run FWD or REV commands must be
removed and then re-applied to start after application of line power.
Keypad STOP Key is active as a Coast to Stop command. To reset
after Keypad Coast to Stop, press Keypad STOP Key again. A
STOP Command is given if a command signal is sensed at the
Control Terminal Strip and then lost.
9
Auto Restart is active after application of line power and Run
Command is given at the Control Terminal Strip. If parameter
21-OPERATING MODE = 2, 3, 4, 5, 6, or 7 then Keypad STOP Key
active as a Coast to Stop command. To reset after Keypad Coast
to Stop, press Keypad STOP Key again. A STOP Command is
given if a command signal is sensed at the Control Terminal Strip
and then lost.
10
Synchro Start and Manual Restart. If parameter 21- OPERATING
MODE = 2, 3, 4, 5, 6, or 7 then Keypad STOP Key active as a
Coast to Stop command. To reset after Keypad Coast to Stop,
press Keypad STOP Key again. A STOP Command is given if a
command signal is sensed at the Control Terminal Strip and then
lost.
11
Synchro Start and Auto Restart. If parameter 21- OPERATING
MODE = 2, 3, 4, 5, 6, or 7 then Keypad STOP Key active as a
Coast to Stop command. To reset after Keypad Coast to Stop,
press Keypad STOP Key again. A STOP Command is given if a
command signal is sensed at the Control Terminal Strip and then
lost.
84-Display Options - Sets the information to be displayed on
the keypad LCD display during Run operation. The display will
always show set frequency in the Stop Mode and while the
output frequency is being set. If set to a value of “0” the display
will indicate Output Frequency (parameter 12-Output
Summary of Contents for ID10101-E
Page 1: ...Series 10 Inverter Control Installation and Operating Manual 2 00 MN710 AC INVERTER ...
Page 13: ...1 8 General Information ...
Page 35: ...2 22 Installation ...
Page 67: ...4 6 Troubleshooting ...
Page 68: ...Section 5 Illustrations Illustrations 5 1 ...
Page 69: ...5 2 Illustrations ...
Page 70: ...Illustrations 5 3 3 5 HP NEMA 1 230 460VAC ...
Page 71: ...5 4 Illustrations ...