2-6 Installation
Recommended Terminal Tightening Torques
Catalog No.
Tightening Torques
Power Terminal TB1
Control Terminal Strip
All Series 10
10 In-Lb (1.13 Nm)
2 In-Lb (0.23 Nm)
Caution:
Do not use this control with any input
voltage other than stated on the control
nameplate. Use of control with wrong power
source can damage the control.
Main Circuit Wiring
M3
M2
M1
L3 *
L2
L1
50/60Hz
3 Phase Power
Heatsink
GND
Heatsink
GND
Breaker or Fuse
Protection customer
provided option
To External
Trip Circuit
T3
T2
T1
GND
Motor
External or remote motor overload protection
may be required by NEC or other regulator codes.
* Note: L3 is not available on 115VAC input models.
See recommended tightening torques for terminal connectors.