![Baldor GLC30 Installation & Operating Manual Download Page 65](http://html1.mh-extra.com/html/baldor/glc30/glc30_installation-and-operating-manual_3577753065.webp)
Operation 4-19
MN2408
Figure 4-5 Main Menu Loop Parameters
Parameter
Setting
Range
System Voltage (Line To Line)
XXXXX VAC
120–15000VAC
System Frequency
50Hz/60Hz
Toggle Between 50/60 Hz
System Phases
1 Phase/3 Phase
Toggle Between 1 & 3 Phase
y
Neutral Connected
Toggle Between Yes/No
Voltage Sensing
Voltage Sensing Pt Ratio
Ratio XXX
Enter Number 1–208 (1=Direct)
Current Sensing
Current Sensing Ct Ratio
Ratio XXX
Enter Number 1–999 (1=Direct)
Temperature Scale
Deg C/Deg F
Toggle Between Deg C/Deg F
Pressure Scale
PSI/KPA
Toggle Between Psi/Kpa
Start Delay
XXX Seconds
0–999 Seconds
Crank Time
XX Seconds
0–99 Seconds
Rest Time
XX Seconds
0–99 Seconds
Starter Re–engage Delay
XX Seconds
0–99 Seconds 0=Disabled
Number Of Cranks
XX Cranks
0–99 Times 0=Continuous
Bypass Delay
XX Seconds
0–99 Seconds
Cool down Delay
XX Seconds
0–9999 Seconds
Nominal RPM
XXXX RPM
0–4000RPM
Flywheel Teeth (Engine Speed
Sensing, Magnetic Pick Up
XXX Teeth
0–999 Teeth
Crank Disconnect
XX %
0–100%
Overspeed
XX %
100–150%
Overspeed Transient
X.X Seconds
0.0–9.9 Seconds
Run Output
Fail Safe Yes/No
Toggle Between Yes/No
Loss Of Speed Signal
Shutdown Alarm/Shutdown
Toggle Between Alarm/Shutdown
Common Fail For
Not In Auto Yes/No
Toggle Between Yes/No
Horn For Not In Auto
Toggle Between Yes/No
Prog Output #1
Common Fail (Factory setting)
Prog Output #2
Common Fail (Factory setting)
Prog Output #3
Common Fail (Factory setting)
Prog Output #4
Common Fail (Factory setting)
Prog Output #5
Common Fail (Factory setting)
Prog Output #6
Common Fail (Factory setting)
Warm–up Delay
0–99 Seconds
Neutral Delay
0–99 Seconds
Return Delay
0–999 Seconds
Reset Run Hours
Access by Master Password Only
Yes/No
Toggle Between Yes/No
Summary of Contents for GLC30
Page 12: ...2 2 General Information MN2408...
Page 32: ...2 22 General Information MN2408...
Page 42: ...3 10 Receiving Installation MN2408 Figure 3 4 Three Phase WYE and DELTA Connections...
Page 52: ...4 6 Operation MN2408 Figure 4 3 Engine Controller Inputs Outputs...
Page 64: ...4 18 Operation MN2408 Figure 4 4 Configuration Data Sheet j j j j j j j j j...
Page 86: ...A 10 Series GLC MN2408 Figure A 2 Customer Interface Connection Diagram MEC20 MEC2...
Page 87: ...Series GLC A 11 MN2408 Figure A 3 Customer Interface w o Breaker Power Connection Diagram...
Page 88: ...A 12 Series GLC MN2408 Figure A 4 Single Phase w o Breaker Connection Diagram...
Page 89: ...Series GLC A 13 MN2408 Figure A 5 Single Phase One Breaker Connection Diagram...
Page 90: ...A 14 Series GLC MN2408 Figure A 6 Single Phase Two Breaker Connection Diagram...
Page 95: ...Series GLC A 19 MN2408 Figure A 11 Three Phase Connection Diagram...
Page 96: ...A 20 Series GLC MN2408 Figure A 12 Three Phase Connection Diagram with PMG...
Page 97: ...Series GLC A 21 MN2408 Figure A 13 Three Phase Connection Diagram Wire 1 0 and larger...
Page 104: ...A 28 Series GLC MN2408 Figure A 20 Control Box Connections with MEC2 Controller...
Page 105: ...Series GLC A 29 MN2408 Figure A 21 Engine Wiring Woodward 4 3L GM...
Page 106: ...A 30 Series GLC MN2408 Figure A 22 Engine Wiring Woodward 5 7L GM...
Page 107: ...Series GLC A 31 MN2408 Figure A 23 Engine Wiring Woodward 8 1L GM...
Page 108: ...A 32 Series GLC MN2408...