![Baldor GLC30 Installation & Operating Manual Download Page 60](http://html1.mh-extra.com/html/baldor/glc30/glc30_installation-and-operating-manual_3577753060.webp)
4-14 Operation
MN2408
Main Menu Loop
Continued
Loss Of Speed Signal
Select the desired action (i.e. alarm or shutdown) when a loss of speed signal is detected during operation.
Note: A loss of speed signal must be detected for longer than 2 seconds to initiate the desired action.
Common Fail For Not In Auto" Function Selects if a common fail alarm condition is to be activated during manual operation.
Horn For Not In Auto
The Horn may be programmed to sound when the controllers operating mode is switched from the Auto position. If the
Horn is not to sound, select program setting No.
Warm-up Delay
The WARM-UP Delay menu appears when the Gen Ready To Load programmable output is selected (typically for AMF
application). Set to the desired time in seconds, which the generator requires to effectively warm-up" before accepting
load. This is typically set for 3 seconds. The Warm-Up Delay is initiated after the generator is above programmed voltage
and frequency limits (per the analog programming menus).
Neutral Delay
The Neutral Delay menu appears when the Utility Ready To Load programmable output is selected (typically for AMF
application). The Neutral Delay timer is used when transferring between the available power sources. When transferring
from the utility supply to the generator supply, the Neutral Delay timer will start when the Utility Ready To Load output
de-energizes. When the Neutral Delay time period expires, the Generator Ready To Load output is energized. The
purpose of the Neutral Delay timer is to prevent out of phase transfers, which may be caused by a fast transfer and the
two sources of supply are out of synchronism. The Neutral Delay timer ensures the load voltages decay before the
transfer is initiated. Set to the desired time in seconds. The Neutral Delay timer is typically set for 3 seconds.
Note: The Neutral Delay feature is only effective when an electrically held contactor-type" transfer switch is connected.
Contact Baldor for further application information on use with other types of transfer switch mechanisms.
Return Delay
The Return Delay menu appears when the Utility Ready To Load output is selected (typically for AMF application). The
Return Delay is initiated when the remote start signal is removed (signaling utility power is available). After the Return
Delay timer expires, the Generator Ready To Load output is removed, and the Utility Ready To Load output energizes to
signal transfer the load back to the utility supply. The purpose of the Return Delay timer is to ensure that the utility power
has returned to a steady state for the selected time period before the load is transferred back to the utility supply. The
Return Delay timer is typically set for 120 seconds.
Caution:
The Programmable Output Contacts selection must agree with the external control wiring
prior to energizing the controller. Failure to do so may cause severe equipment damage.
Programmable Output Contacts Select the desired function that will activate the programmable relay output contact.
One of the following functions may be selected:
Energize To Stop
Gen Ready To Load
Air Flap Eps Supplying Load
Utility Ready To Load
Oil Bypass Timer Complete
Common Fail
Digital Faults #1 to4
Switch Not In Auto
Overspeed
Engine Ready
Loss Of Speed Signal
Engine Run (Fuel)
Low Bat Voltage
Preheat High Bat Voltage
Engine Running
Weak Bat Voltage
ATS Test
Low Oil Press #1 Alarm
Common Alarm
Common Shutdown
Low Oil Press #2 Shutdown
High Eng Temp #1 Alarm
High Eng Temp #1 Shutdown
Reset Run Hours
The hourmeter may be reset to zero hours when yes is programmed.
Note: This programming prompt is only accessible while using the Master" programming security password.
Analog Fault Menu Loop
The controller’s analog fault settings are described as follows:
Level
Sets the actual analog signal setpoint at which the selected fault type will be activated.
Note: For AC voltage fault circuits, two levels (i.e. pick-up & drop-out) must be programmed.
Action
Allows a fault to be either an Alarm fault or a Shutdown fault.
Alarm Latch
If an fault was set as an Alarm, it may be selected as a Latching" alarm or Non-latching" alarm. A Latching alarm is not
cleared until a reset command clears it.
Note: This value only appears if alarm faults are programmed. Shutdown faults are automatically set as latching.
Bypass On Start Delay
Allows the alarm or shutdown fault to be disabled until after the bypass timer has expired. Faults that are not delayed are
enabled at all times (i.e. engine running or stopped).
Transient Delay Times
Allows the selected fault to be disabled until the delay period has expired. Delay times are 0.0 to 999.9 seconds.
Summary of Contents for GLC30
Page 12: ...2 2 General Information MN2408...
Page 32: ...2 22 General Information MN2408...
Page 42: ...3 10 Receiving Installation MN2408 Figure 3 4 Three Phase WYE and DELTA Connections...
Page 52: ...4 6 Operation MN2408 Figure 4 3 Engine Controller Inputs Outputs...
Page 64: ...4 18 Operation MN2408 Figure 4 4 Configuration Data Sheet j j j j j j j j j...
Page 86: ...A 10 Series GLC MN2408 Figure A 2 Customer Interface Connection Diagram MEC20 MEC2...
Page 87: ...Series GLC A 11 MN2408 Figure A 3 Customer Interface w o Breaker Power Connection Diagram...
Page 88: ...A 12 Series GLC MN2408 Figure A 4 Single Phase w o Breaker Connection Diagram...
Page 89: ...Series GLC A 13 MN2408 Figure A 5 Single Phase One Breaker Connection Diagram...
Page 90: ...A 14 Series GLC MN2408 Figure A 6 Single Phase Two Breaker Connection Diagram...
Page 95: ...Series GLC A 19 MN2408 Figure A 11 Three Phase Connection Diagram...
Page 96: ...A 20 Series GLC MN2408 Figure A 12 Three Phase Connection Diagram with PMG...
Page 97: ...Series GLC A 21 MN2408 Figure A 13 Three Phase Connection Diagram Wire 1 0 and larger...
Page 104: ...A 28 Series GLC MN2408 Figure A 20 Control Box Connections with MEC2 Controller...
Page 105: ...Series GLC A 29 MN2408 Figure A 21 Engine Wiring Woodward 4 3L GM...
Page 106: ...A 30 Series GLC MN2408 Figure A 22 Engine Wiring Woodward 5 7L GM...
Page 107: ...Series GLC A 31 MN2408 Figure A 23 Engine Wiring Woodward 8 1L GM...
Page 108: ...A 32 Series GLC MN2408...