![Baldor GLC30 Installation & Operating Manual Download Page 45](http://html1.mh-extra.com/html/baldor/glc30/glc30_installation-and-operating-manual_3577753045.webp)
Receiving & Installation 3-13
MN2408
Figure 3-6 Battery Installation
Washers & Nut
Battery
Battery Hold Down Rod
Washers & Nut
Battery Tray
The + and – terminals of your battery may
be different than shown. Be sure that the
Positive lead is connected to the positive
(+) terminal of your battery.
Battery Hold Down Bar
(Install away from terminals)
4.
Connect the positive lead to the positive (+) battery terminal.
5.
Connect the negative lead to the negative (–) battery terminal.
6.
Do not lay tools or metal parts on top of batteries.
7.
Connect charging source to the battery terminals.
8.
Disconnect the battery’s ground terminal before working in the vicinity of the battery or
battery wires. Contact with the battery can result in electrical shock when a tool
accidently touches the positive battery terminal or wire. The risk of such shock is
reduced when the ground lead is removed during installation and maintenance.
Recommended Engine Oil and Battery Type
When replacing batteries, use only the recommended battery for your generator, see Table 3-7.
Table 3-7
MODEL
SUMMER
WINTER
OIL
RECOMMENDED
(AMPS) COLD
MODEL
SUMMER
OIL
WINTER
OIL
OIL
CAPACITY
RECOMMENDED
BATTERY
(AMPS) COLD
CRANKING
GLC30
SAE. 30
5W/30
6.0 QTS
BCI Group 31
925
GLC35
SAE. 30
5W/30
6.0 QTS
BCI Group 31
925
GLC45
SAE. 30
5W/30
6.0 QTS
BCI Group 31
925
GLC50
SAE. 30
5W/30
6.2 QTS
BCI Group 31
925
GLC60
SAE. 30
5W/30
6.2 QTS
BCI Group 31
925
GLC80
SAE. 30
5W/30
6.5 QTS
BCI Group 31
925
GLC100
SAE. 30
5W/30
6.5 QTS
BCI Group 31
925
GLC125
SAE. 30
5W/30
6.5 QTS
BCI Group 31
925
Post Installation Checks
When the initial installation is complete, these checks must be performed before starting the
engine. These checks are not required before each start, only after the initial installation.
1.
Generators that have been in transit or storage for long periods may be subjected to
extreme temperature and moisture changes. This can cause excessive condensation,
and the generator windings should be thoroughly dried before bringing the generator
up to full nameplate voltage. If this precaution is not taken, serious damage to the
generator can result.
Caution:
Do not apply high voltage to windings (do not start the generator) in a moisture–saturated
condition. Moisture can cause insulation breakdown, making it necessary to return the
generator to the factory for repair, and consequent expense and loss of time.
Note: These precautions are especially necessary in locations such as seaboard installations
and other high humidity areas. Some installations will be in atmospheres that are much
more corrosive than others. Prevention of a failure is better than being forced to make a
repair.
Summary of Contents for GLC30
Page 12: ...2 2 General Information MN2408...
Page 32: ...2 22 General Information MN2408...
Page 42: ...3 10 Receiving Installation MN2408 Figure 3 4 Three Phase WYE and DELTA Connections...
Page 52: ...4 6 Operation MN2408 Figure 4 3 Engine Controller Inputs Outputs...
Page 64: ...4 18 Operation MN2408 Figure 4 4 Configuration Data Sheet j j j j j j j j j...
Page 86: ...A 10 Series GLC MN2408 Figure A 2 Customer Interface Connection Diagram MEC20 MEC2...
Page 87: ...Series GLC A 11 MN2408 Figure A 3 Customer Interface w o Breaker Power Connection Diagram...
Page 88: ...A 12 Series GLC MN2408 Figure A 4 Single Phase w o Breaker Connection Diagram...
Page 89: ...Series GLC A 13 MN2408 Figure A 5 Single Phase One Breaker Connection Diagram...
Page 90: ...A 14 Series GLC MN2408 Figure A 6 Single Phase Two Breaker Connection Diagram...
Page 95: ...Series GLC A 19 MN2408 Figure A 11 Three Phase Connection Diagram...
Page 96: ...A 20 Series GLC MN2408 Figure A 12 Three Phase Connection Diagram with PMG...
Page 97: ...Series GLC A 21 MN2408 Figure A 13 Three Phase Connection Diagram Wire 1 0 and larger...
Page 104: ...A 28 Series GLC MN2408 Figure A 20 Control Box Connections with MEC2 Controller...
Page 105: ...Series GLC A 29 MN2408 Figure A 21 Engine Wiring Woodward 4 3L GM...
Page 106: ...A 30 Series GLC MN2408 Figure A 22 Engine Wiring Woodward 5 7L GM...
Page 107: ...Series GLC A 31 MN2408 Figure A 23 Engine Wiring Woodward 8 1L GM...
Page 108: ...A 32 Series GLC MN2408...