Figure 4‐17 Main Menu Loop Parameters
Parameter
Setting
Range
System Voltage (Line To Line)
XXXXX VAC
120-15000V AC
System Frequency
50Hz/60Hz
Toggle Between 50/60 Hz
System Phases
1 Phase/3 Phase
Toggle Between 1 & 3 Phase
Neutral Connected
Toggle Between Yes/No
Voltage Sensing
Voltage Sensing Pt Ratio
Ratio XXX
Enter Number 1-208 (1=Direct)
Current Sensing
Current Sensing Ct Ratio
Ratio XXX
Enter Number 1-999 (1=Direct)
Temperature Scale
Deg C/Deg F
Toggle Between Deg C/Deg F
Pressure Scale
PSI/KPA
Toggle Between Psi/Kpa
Start Delay
XXX Seconds
0-999 Seconds
Crank Time
XX Seconds
0-99 Seconds
Rest Time
XX Seconds
0-99 Seconds
Starter Re-engage Delay
XX Seconds
0-99 Seconds 0=Disabled
Number Of Cranks
XX Cranks
0-99 Times 0=Continuous
Bypass Delay
XX Seconds
0-99 Seconds
Cool down Delay
XX Seconds
0-9999 Seconds
Nominal RPM
XXXX RPM
0-4000RPM
Flywheel Teeth (Engine Speed
Sensing, Magnetic Pick Up
XXX Teeth
0-999 Teeth
Crank Disconnect
XX %
0-100%
Overspeed
XX %
100-150%
Overspeed Transient
X.X Seconds
0.0-9.9 Seconds
Run Output
Fail Safe Yes/No
Toggle Between Yes/No
Loss Of Speed Signal
Shutdown Alarm/Shutdown
Toggle Between Alarm/Shutdown
Common Fail For
Not In Auto Yes/No
Toggle Between Yes/No
Horn For Not In Auto
Toggle Between Yes/No
Prog Output #1
Common Fail (Factory setting)
Prog Output #2
Common Fail (Factory setting)
Prog Output #3
Common Fail (Factory setting)
Prog Output #4
Common Fail (Factory setting)
Prog Output #5
Common Fail (Factory setting)
Prog Output #6
Common Fail (Factory setting)
Warm-up Delay
0-99 Seconds
Neutral Delay
0-99 Seconds
Return Delay
0-999 Seconds
Reset Run Hours
Access by Master Password Only
Yes/No
Toggle Between Yes/No
Summary of Contents for GLC10
Page 12: ...2 2 General Information MN2408...
Page 24: ...2 14 General Information MN2408...
Page 40: ...3 16 Receiving Installation MN2408...
Page 58: ...4 18 Operation MN2408 Figure 4 15 Engine Controller Inputs Outputs...
Page 70: ...4 30 Operation MN2408 Figure 4 16 Configuration Data Sheet j j j j j j j j j...
Page 74: ...4 34 Operation MN2408...
Page 88: ...A 10 Series GLC MN2408...
Page 90: ...B 2 Series GLC MN2408 Figure B 11 Customer Interface Connection Diagram MEC20 MEC2...
Page 91: ...Series GLC B 3 MN2408 Figure B 12 Customer Interface w o Breaker Power Connection Diagram...
Page 92: ...B 4 Series GLC MN2408 Figure B 13 Single Phase w o Breaker Connection Diagram...
Page 93: ...Series GLC B 5 MN2408 Figure B 14 Single Phase One Breaker Connection Diagram...
Page 94: ...B 6 Series GLC MN2408 Figure B 15 Single Phase Two Breaker Connection Diagram...
Page 99: ...Series GLC B 11 MN2408 Figure B 20 Three Phase Connection Diagram...
Page 100: ...B 12 Series GLC MN2408 Figure B 21 Three Phase Connection Diagram with PMG...
Page 101: ...Series GLC B 13 MN2408 Figure B 22 Three Phase Connection Diagram Wire 1 0 and larger...
Page 106: ...B 18 Series GLC MN2408 Figure B 27 Control Box Connections with MEC20 Controller...
Page 107: ...Series GLC B 19 MN2408 Figure B 28 Control Box Connections with MEC20 Controller Governor...
Page 108: ...B 20 Series GLC MN2408 Figure B 29 Control Box Connections with MEC2 Controller...
Page 109: ...Series GLC B 21 MN2408 Figure B 30 Engine Wiring Woodward 4 3L GM...
Page 110: ...B 22 Series GLC MN2408 Figure B 31 Engine Wiring Woodward 5 7L GM...
Page 111: ...Series GLC B 23 MN2408 Figure B 32 Engine Wiring Woodward 8 1L GM...
Page 112: ...B 24 Series GLC MN2408...
Page 113: ...Baldor District Offices...