4‐6 Operation
MN2408
Analog Inputs
Three analog inputs for resistive sensor 0 to 2400 ohms measuring are available on IL controller.
Use LiteEdit software to modify configuration.
The Analog inputs values assignment (AI1 = Oil press, AI2 = Water temp, AI3 = Fuel level) is fix.
It is possible to configure on each Analog input:
Reading from IL Analog inputs or from Engine Control Unit via CAN bus (J1939)
Sensor characteristics - from the list,
Value dimension (e.g. psi - bars,
°
F -
°
C, % - l)
Number of decimal points (0, 1, 2,
...
).
Note: Corresponding Analog input terminal is dead when reading is switched to ECU.
All values from ECU shall show ####, but no alarm is displayed when CAN communication
is interrupted.
Warning and shut-down limits are adjusted in Engine protection group.
Table 4‐13 Analog Inputs
AI1 Oil press
Oil pressure analog input. Default VDO sensor in range 0 to 145 psi.
AI2 Water temp
Water temperature analog input. Default VDO sensor in range 32 to 212
°
F
AI3 Fuel level
Fuel level analog input. Default VDO sensor 0-180R = 0-100%.
Set points
Table 4‐14 Basic Setpoints
EnterPassword
Password is a four-digit number. Password enables change of relevant
protected set points Use
⇑
or
⇓
keys to set and ENTER key to enter the
password.
ChangePassword
Use
⇑
or
⇓
keys to set and ENTER key to change the password.
Gen-set name
User defined name, used for InteliLite identification at remote phone or
mobile connection. Gen-set name is max 14 characters long and have to
be entered using LiteEdit software.
Nomin power(3ph)
Nominal power of the generator in three phases connection.
Step: 1 kW; Range: 1 - 3000 kW
Nomin power(1ph)
Nominal power of the generator in single-phase connection.
Step: 1 kW; Range: 1 - 3000 kW
CT Ratio
Gen-set phases current transformers ratio.
Step: 1 A; Range: 1 - 5000 A / 5A
PT ratio
Gen-set potential transformers ratio.
Step: 0,1 V / V; Range: 0,1 - 500,0 V / V
Nominal freq
Nominal generator frequency (usually 50 or 60 Hz )
Step: 1Hz; Range: 45 - 65 Hz
Gear teeth
Number of teeth on the engine gear for the pick-up. Set to zero, if no
pick-up is used. Engine speed is counted from the generator frequency.
Step: 1; Range: 0 - 500
Note: Generator frequency can be used only when generator voltage
(min 5V) is present before reaching of the firing speed
(Starting RPM) after start.
Nominal RPM
Nominal engine speed. Step: 1RPM; Range: 100 - 4000 RPM.
FLTRESGOTOMAN
DISABLED: Controller stays in AUT mode after Fault reset .
ENABLED: Automatic switch from AUT (or TEST) to MAN mode after
Fault reset to avoid automatic engine start. This function is active for Shut
down protection only.
DispBackLightTO
Timeout after which the display backlight is switched off.
Step: 1 min Range: 0 - 60 min
Default value: 0 = the display lights all the time
Mode IL [ OFF, MAN, AUT ]
Equivalent to Controller mode changes by MODE
or MODE
buttons.
Note: Controller Mode change can be separately password protected.
RS232 mode
[Standard/Modbus ]
Communication protocol switch.
Standard: LiteEdit communication protocol. Modbus: Modbus protocol.
Note: For detail description see chapter Modbus protocol.
Num rings AA
Number of rings prior to open modem connection. Step: 1; Range: 1 - 30
Note: NumberRings AA change is not activated immediately. It is activated
after controller is switched on or when modem is connected to controller.
Summary of Contents for GLC10
Page 12: ...2 2 General Information MN2408...
Page 24: ...2 14 General Information MN2408...
Page 40: ...3 16 Receiving Installation MN2408...
Page 58: ...4 18 Operation MN2408 Figure 4 15 Engine Controller Inputs Outputs...
Page 70: ...4 30 Operation MN2408 Figure 4 16 Configuration Data Sheet j j j j j j j j j...
Page 74: ...4 34 Operation MN2408...
Page 88: ...A 10 Series GLC MN2408...
Page 90: ...B 2 Series GLC MN2408 Figure B 11 Customer Interface Connection Diagram MEC20 MEC2...
Page 91: ...Series GLC B 3 MN2408 Figure B 12 Customer Interface w o Breaker Power Connection Diagram...
Page 92: ...B 4 Series GLC MN2408 Figure B 13 Single Phase w o Breaker Connection Diagram...
Page 93: ...Series GLC B 5 MN2408 Figure B 14 Single Phase One Breaker Connection Diagram...
Page 94: ...B 6 Series GLC MN2408 Figure B 15 Single Phase Two Breaker Connection Diagram...
Page 99: ...Series GLC B 11 MN2408 Figure B 20 Three Phase Connection Diagram...
Page 100: ...B 12 Series GLC MN2408 Figure B 21 Three Phase Connection Diagram with PMG...
Page 101: ...Series GLC B 13 MN2408 Figure B 22 Three Phase Connection Diagram Wire 1 0 and larger...
Page 106: ...B 18 Series GLC MN2408 Figure B 27 Control Box Connections with MEC20 Controller...
Page 107: ...Series GLC B 19 MN2408 Figure B 28 Control Box Connections with MEC20 Controller Governor...
Page 108: ...B 20 Series GLC MN2408 Figure B 29 Control Box Connections with MEC2 Controller...
Page 109: ...Series GLC B 21 MN2408 Figure B 30 Engine Wiring Woodward 4 3L GM...
Page 110: ...B 22 Series GLC MN2408 Figure B 31 Engine Wiring Woodward 5 7L GM...
Page 111: ...Series GLC B 23 MN2408 Figure B 32 Engine Wiring Woodward 8 1L GM...
Page 112: ...B 24 Series GLC MN2408...
Page 113: ...Baldor District Offices...