Section 4
Operation
Operation 4-1
MN2414
Operator Control Panel
Each operator panel is slightly different, depending on features of the generator you purchased.
The Operator Control Panel of Figure 4-1 is shown because it has most of the available features.
This will be used to explain how the controls operate.
Figure 4-1 Operator Control Panel
Start Switch
(not shown) Push to engage the engine starter (if Run Switch is in the ON position).
Run Switch
(not shown) OFF
−
Turns off the engine (kill switch).
ON
−
Allows the engine to start and run for normal operation.
For DG3E, a Run/Stop lever is used where Run = On, Stop = Off.
Elapsed Time
An hour meter that measures the total hours the generator has been in use (engine
running).
AC Voltmeter
Displays the voltage level at the output of the generator (the 230VAC output).
AC Circuit Breakers
Provide overcurrent protection for the generator output. When tripped, the plunger (in
center of breaker) will extend out about 3/8 inch. Remove the loads, push the plunger
into the breaker to reset the breaker the restore the loads.
WARNING: Never connect this generator to any buildings electrical system unless a licensed electrician
has installed an approved transfer switch. The National Electrical Code (NEC) requires that
connection of a generator to any elastical circuit normally powered by means of an electric
utility must be connected by means of approved transfer switch equipment so as to isolate
the electrical circuit from the utility distribution system when the generator is operating.
Failure to isolate the electrical circuits by such means may result in injury or death to utility
power workers due to backfeed of electrical energy onto the utility lines.
Receptacles
−
Receptacles are provided to allow easy connection of electrical loads. Never connect this
generator to any buildings electrical system unless a licensed electrician has installed an
approved transfer switch. Multiple receptacles may be used at the same time provided the total
electrical load does not exceed the generators rated output.
120Volts
−
NEMA
5
−
20R GDCI Duplex receptacle provides ground fault protection.
Rated 125VAC at 20 Amperes.
30 Amps 120 Volts
−
Twist lock NEMA L5
−
30R receptacle, rated 125 Volts at 30 Amperes.
30 Amps 120/240 Volts
−
Twist lock NEMA L14
−
30R receptacle rated 250Volts at 30 Amperes.
Note: The nominal voltage produced by the generator at each receptacle is 120VAC or 240VAC.
Summary of Contents for DG3E
Page 1: ...Diesel POW R Products Generator DG3E and DG6E Installation Operating Manual 5 05 MN2414...
Page 4: ...ii Table of Contents MN2414...
Page 12: ...2 2 General Information MN2414...
Page 26: ...A 4 Premier K Series MN2414 Figure A 5 DG3E Wiring Diagram...
Page 27: ...Premier K Series A 5 MN2414 Figure A 6 DG3E Wiring Diagram with Low Oil Remote Start...
Page 28: ...A 6 Premier K Series MN2414 Figure A 7 DG6E Wiring Diagram...