34 |
© 2021 Baker Hughes Company. All rights reserved.
2.
Connect the 4 - 20 mA input signal and the optional switches or position retransmit by:
a.
Stripping the insulation at the end of both wires 0.43” / 11 mm.
b. Inserting the stripped end of the wires fully in to the appropriate terminal. Loosen the
terminal screw if required to insert the wire.
Refer to the label next to each screw terminal to determine the function of the terminal
and correct polarity (see Figure 19 for 4 - 20 mA connections and Figure 20 on page 34
for position retransmit).
c.
Tightening the terminal screws (to a torque of 5 to 7 lb·in).
Figure 19 - Connections to Electronics Module with Switches (via Interface Board)
Figure 20 - Connections to Electronics Module with Position Retransmit
(via Interface Board)
Optional Solid State
Switches
4-20 mA Input Signal
Ground
Ground
4-20 mA Input Signal
(4 - 20 mA Control Loop)
4-20 mA Input Signal
(Retransmit signal)