© 2021 Baker Hughes Company. All rights reserved. Masoneilan SVi1000 Positioner Quick Start Guide | 25
Table 2: Travel Sensor Alignment
Rotary
Mounting
System
Stroke Direction
Magnet
Orientation
Valve
Position
Sensor
Counts
Rotary
<60° Rotation
Clockwise or
counterclockwise
rotation
(0°)
Closed (0%)
0 +/- 1000
>60° Rotation
Clockwise with
increasing setpoint
(-45°)
Full Open
or
Full Closed
-8000 +/- 1500
or
+8000 +/- 1500
>60° Rotation
Counter Clockwise
rotation with increasing
setpoint
(+45°)
Full Open
or
Full Closed
-8000 +/- 1500
or
+8000 +/- 1500
General Rule
for other
con figurations
Any amount of
rotation Clockwise or
counterclockwise
(0°)
50%
Travel
(Mid-Stroke)
0 +/- 1000
CAUTION
Do not carry the positioner by the alignment ring.
Figure 11 - Camflex V-Seal
Align the end of the magnet holder assembly with
the end of the mounting bracket
V-Seal in contact with
the alignment ring
Alignment
ring
V-Seal