5 Test Procedure
44
DHV0078 b2 EN
©
b2 electronic
GmbH
Running an automatic test – detailed steps
Steps
AR1-AR9
describe how to
run a test in the automatic mode.
Step
Procedure
(run automatic test)
Example
AR1:
Use Last Seq. or
Start New Test
To repeat the previous test sequence:
•
Select “Use Last Test Sequence” from “Main Menu”
•
Proceed to step AR5
Otherwise, select:
•
“Start a new Test”
AR2:
De-/activate
Reporting
To activate reporting:
•
Select “YES”, See 6 – Reporting
To conduct a test without generating a report:
•
Select “NO”
AR3:
(If Reporting
active: this step
follows report
setup completion)
To run an test sequence:
•
Select “Auto Seq”
AR4:
Select sequence
•
Select the appropriate test sequence
•
To continue, select “NEXT”
AR5:
Parameter
verification
•
Verify that the selected sequence defines the
correct test parameters
To run the auto test sequence:
•
Select “START” from the bottom of the screen
AR6:
HV activation
Once the activation screen appears,
•
Press the HV switch
within 10 seconds.
If the HV switch is not activated within the 10-second
window, the “Start Auto Test Seq.” screen will reappear.
USB - Main Menu – HVA120
Use Last Test Seq.?
3.0kV Maint. C. HYBR (T)
Start a New Test
Manual Mode
Reports & Setup
13.3.2009 10:23
Start a New Test
Do you want to
store a report?
Yes
No
MAIN
Start a New Test
Use an existing
Auto Test Sequence
or use Manual Mode?
Auto Seq.
Manual
MAIN PREV
Select Auto Test Seq.
3.0kV Maint. C. HYBR (T)
1.0kV Maint. C. XLPE (T)
BACK SELECT NEXT
Start Auto Test Seq.
1.0 kV Cable XPLE
Maintenance Test Sequence
Test Voltage: 1.0kVrms
Duration: 15 min
Waveform: Sine 0.1Hz
Trip out on
Reporting Active
MAIN BACK
START
ATTENTION
High Voltage!
Press I/O Button to
switch ON High Voltage
Summary of Contents for HVA120
Page 2: ...1 Introduction 2 DHV0078 b2 EN b2 electronic GmbH...
Page 11: ...2 Safety b2 electronic GmbH DHV0078 b2 EN 11...
Page 33: ...5 Test Procedure b2 electronic GmbH DHV0078 b2 EN 33 Connection diagram vacuum bottle test...
Page 47: ...5 Test Procedure b2 electronic GmbH DHV0078 b2 EN 47 5 5 Discharge Status...
Page 63: ...11 Declaration of Conformity b2 electronic GmbH DHV0078 b2 EN 63 HVA30 5...
Page 64: ...11 Declaration of Conformity 64 DHV0078 b2 EN b2 electronic GmbH HVA30 7 HVA40 5 HVA54 3...
Page 65: ...11 Declaration of Conformity b2 electronic GmbH DHV0078 b2 EN 65 HVA54 5...
Page 66: ...11 Declaration of Conformity 66 DHV0078 b2 EN b2 electronic GmbH HVA60...
Page 67: ...11 Declaration of Conformity b2 electronic GmbH DHV0078 b2 EN 67 HVA68 2...
Page 68: ...11 Declaration of Conformity 68 DHV0078 b2 EN b2 electronic GmbH HVA90 HVA94...
Page 69: ...11 Declaration of Conformity b2 electronic GmbH DHV0078 b2 EN 69 HVA120...