System data parameters
Section 1 – Operating Instructions
Rev. 2.8 Date 2019-02-04
Software version 1.00
CCS
Chapter 8
Page 8-3
8.5
Container reset, menu item 3
8.6
Pressure alarm reset, menu item 4
8.7
Service interval, menu item 5
Only the empty containers are displayed.
Reset
Reset fault message
(only possible when level switch “on”).
3 Container Reset
C1.1 Reset
C1.2 Reset
C2.1 Reset
C2.2 Reset
C3.1 Reset
C3.2 Reset
Esc
Enter
A pressure alarm can be acknowledged after the cause has been
eliminated.
Reset
Reset of the fault message.
Minimum pressure:
active after pump start-up, malfunction when the actual value is smaller
than 0.1 bar for longer than 1.0 second, no automatic restart.
Pressure low:
active after switch-on monitoring, malfunction when the actual value
is smaller than (reference value -0.3 bar) for longer than 2.0 minutes,
no automatic restart.
Pressure high:
active after switch-on monitoring, malfunction when the actual value
is greater than (reference value +0.2 bar) for longer than 1.2 seconds,
automatic restart possible 3 times within 5 minutes.
Maximum pressure:
active after switch-on monitoring, malfunction when the actual value
is greater than (reference value +0.4 bar) for longer than 1.0 second,
no automatic restart
4 Reset alarms
Esc
Enter
xx.xx.xx = Next due date for routine check.
Reset
Timer reset, new value is the current date plus service interval
in accordance with menu 6.8.
5 Service interval
xx.xx.xx
Esc Reset