31
Chapter 4. Explanation of Operation
z
Operation during interlock (interlock activation during RUN)
If the interlock contacts are OFF, lockout occurs and an alarm is issued.
“
E0
” (interlock) and “
P8
” are displayed alternately.
*
Power supply
Burner start contacts
Interlock
Flame signal
Ignition transformer
Pilot valve
Main valve
Flame monitor output
Alarm output
SHUT
FL
AL
Input
Load output
LED indication
Standby
Start
check
Ignition trial
Pilot only
Main trial
Run
Lockout
Flame failure
response
Sequence display
Prepurge
E0 P8
P8
P6
P5
P4
* ON in the case of a direct ignition model, OFF in the case of an interrupted pilot model.
This is because the AUR455 has one output with different operation depending on the type of model, while the AUR450
has two outputs for the pilot valve, one for the intermittent and one for the interrupted type.
z
Operation during interlock (interlock activation between standby and start signal)
Even if the interlock contacts turn OFF before the start contact input, lockout does
not occur.
If the start signal is input in this state, lockout occurs and an alarm is issued. “
E0
”
(interlock) and “
P
1
” are displayed alternately.
Power supply
Burner start contacts
Interlock
Flame signal
Ignition transformer
Pilot valve
Main valve
Flame monitor output
Alarm output
SHUT
FL
AL
Input
Load output
LED indication
Standby
Lockout
Sequence display
Prepurge
E0 P 1