Chapter 6. Maintenance and Inspection
What to do if E951 occurs
E951 occurs when the data read from the burner controller’s EEPROM is abnormal.
In order to write data correctly into the EEPROM, the following operations are
required before and after resetting E951.
(1) If E951 occurs, do not reset the error immediately.
(2) Write correct data to event settings, AUR tag, and AUR memo using the Smart
Loader Package (SLP-A55).
(3) When writing is complete, reset the E951 error.
(4) If any other error occurs, reset it.
(5) Wait for 5 seconds after the reset. If there is no error message, turn off the
power of the burner controller.
(6) Turn the power back on. Wait for 5 seconds after “
-
-
” is displayed on the
7-segment LED. If there is no error message, the settings have been properly
stored in the EEPROM. If E951 occurs again, repeat the operation from step 1.
E951 occurs when data was not properly saved to the burner controller due to
power shutoff or cable removal during data writing, due to an EEPROM error, etc.
After giving a command to write the settings to the burner controller, do not turn
off the burner controller until the writing completion message is displayed in the
Smart Loader Package (SLP-A55).