Chapter 6. Maintenance and Inspection
Alarm
code
Sub-
code
Description
Status
Cancellation method
E9
52
Internal error EEPROM write
Error while writing to the EEPROM
Reset
E9
53
Internal error process data value Internal memory error
Reset
E9
54
System error (1)
CPU communication error
Reset
E9
55
Internal error (input-circuit)
Detection of part failure (voltage applied to
the input terminals by wrong wiring) or strong
inductive electrical noise to the signal wire
Reset
E9
56
Internal error (input-circuit)
Internal clock error
Reset
E9
57
Internal error
(EEPROM data value)
An error was found in CPU mutual check.
There are discrepancies in EEPROM data.
Reset
E9
58
Internal error
(CPU mutual check)
An error was found in the CPU internal status
mutual check.
Reset
E9
60
Internal error
(CPU mutual check)
An error was found in the CPU process status
mutual check.
Reset
E9
6
1
Internal error
(CPU mutual check)
CPU process synchronization error
Reset
E9
62
Internal error (Alarm timeout) Internal feedback signal error of alarm output relay Reset
E9
63
Internal error
(CPU mutual check)
Internal memory data error
•
While settings were being written with the
Smart Loader Package (SLP-A55), the power
was turned OFF or the loader cable was
removed.
Write settings using the
Smart Loader Package
(SLP-A55), and then do a
reset.
E9
64
Internal error (flame circuit)
Error in the circuit for diagnosing the flame
detection circuit
Reset
E9
65
Internal error (flame circuit)
Error in the interactive diagnosis of the flame
detection circuit
Reset
E9
66
Internal error (K1 circuit)
Internal fuse burn-out, or internal feedback
signal error
Reset
E9
67
Internal error (K2 circuit)
Internal feedback signal error
Reset
E9
68
Internal error (PV circuit)
Internal feedback signal error
Reset
E9
69
Internal error (MV circuit)
Internal feedback signal error
Reset
E9
70
Internal error (IG circuit)
Internal feedback signal error
Reset
E9
7
1
Internal error
(Communication setting)
Internal memory error in host communication
setting
•
In turn-down test or communication setting
mode, the power was turned off during
configuration (when the 7-segment display
was blinking), and data was not saved
correctly to the EEPROM.
•
Data was not correctly saved to the EEPROM
with the Smart Loader Package (SLP-A55)
because the power was turned OFF or the
loader cable was removed while settings
were being written, etc.
•
Due to some other failure of the EEPROM,
data was not correctly saved.
Reset the error.
The reset operation
initializes the
communication settings.
Please rewrite them with
the correct values.
See
test and communication
setting modes (Page 20).
Note
•
If a sequence cannot be identified, the sequence code where lockout occurred
may be “
--
” (stopped).
•
If lockout occurs even if the alarm is reset several times, there is a problem with
the product.