24. Press “ESC” twice to return back to the time and date display
Please call AXI International with any questions.
FUEL LINE LEAK
If fuel is detected in the spill / drip tray, the float switch will activate the fuel leak alarm illuminating the
“LEAK DETECTION” indicator. The solenoid will close and the system will remain locked out of operation
until the leak has been corrected and the “ALARM RESET” button has been pushed.
Before removing the spilled fuel from the basin, turn the key switch to the “OFF” position.
Always make sure to find the cause of the leakage and correct it. After removing the spilled fuel, allowing
the leak switch to return to its normal position, the key switch can be returned to the “AUTO” or “RUN”
mode.
Note: Disposal of fuel and associated waste should be done in accordance with Federal, State
and Local regulations.
STABILIZING AND OPTIMIZING FUEL QUALITY
We recommend treating the fuel with the
AXI INTERNATIONAL Fuel Catalyst (AFC-705)
. This will
enhance and accelerate the tank cleaning process by breaking down and dissolving existing tank sludge.
AFC-705 will decontaminate compartments of the tank that are out of reach of the suction line.
Depending on the condition of the fuel and the amount of sludge build-up, it is recommended to initially
use a double dose of one to twenty-five hundred (1:2500) instead of one to five thousand (1:5000) This
has proven to be essential in accelerating the tank cleaning process. AFC-705 contains detergent,
surfactant, dispersant, corrosion inhibitor, lubricity enhancer and combustion catalyst. It does not contain
biocides. AFC-705 should always be used periodically in particular to stabilize fuel that is stored for longer
periods of time.
Note: In cases of severe tank contaminant build-up (sludge) and high water level in bottom, it
is recommended to clean the tank (vacuum bottom) and polish the fuel before initial
use of an STS system.