MICROFAST

®

 QUICK 

RESPONSE UPRIGHT 

SPRINKLER VK3271 (K4.2)

TECHNICAL DATA

Page 1 of 3

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.

Form No. F_061614     18.11.05     Rev 17.2.P65

1.  DESCRIPTION

The Viking Microfast

®

 Quick Response Upright Sprinkler VK3271 is a small, 

thermosensitive, glass-bulb spray sprinkler available in several different finishes 

and temperature ratings to meet design requirements. The special Polyester 

coatings can be used in decorative applications where colors are desired. In 

addition, these coatings have been investigated for installation in corrosive 

atmospheres and are listed as corrosion resistant as indicated in the Approval 

Charts.

2.  LISTINGS AND APPROVALS

VdS approved: 

Certificate: G4930039

CE certified: 

Standard EN 12259-1, EC-certificate of conformity 0786-

CPD-40131

3.  TECHNICAL DATA

Specifications:

Minimum Operating Pressure: 7 psi (0.5 bar)* 

Maximum Working Pressure: 175 psi (12 bar) wwp. 

Factory tested hydrostatically to 500 psi (34.5 bar)

Testing: U.S.A. Patent No. 4,831,870

Thread size: 10 mm BSP

Nominal K-Factor: 4.2 U.S. (57 metric**)

 

Glass-bulb fluid temperature rated to -65 °F (-55 °C)

Overall Length: 2-1/4” (58 mm)

 *cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE 

Approvals ONLY is 5 psi (0.35 bar). 

Material Standards:

Frame Casting: Brass UNS-C84400 or QM Brass

Deflector: Brass UNS-C26000

Bushing: Brass UNS-C36000

Bulb: Glass, nominal 3 mm diameter

Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape

Screw: Brass UNS-C36000

Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400

Pip Cap Attachment: Brass UNS-C36000

For Polyester Coated Sprinklers:

 

Belleville Spring-Exposed

Ordering Information:

 (Also refer to the current Viking price list.)

Order Viking Microfast

®

 Quick Response Upright Sprinkler VK3271 by first adding the appropriate suffix for the sprinkler finish and 

then the appropriate suffix for the temperature rating to the sprinkler base part number. 

Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, and Black Polyester = M-/B

Temperature Suffix (°F/°C): 135°/57° = A, 155°/68° = B, 175°/79° = D, 200°/93° = E, and 286°/141° = G

For example, sprinkler VK3271 with a 1/2” NPT thread, Brass finish and a 155 °F/68 °C temperature rating = Part No. 06931BAB

Available Finishes And Temperature Ratings: 

Refer to Table 1.

Accessories:

 (Also refer to the Viking website.)

Sprinkler Wrench: 

Standard Wrench: Part No. 21475M/B (available since 2017)

 

Sprinkler Cabinets:

A. Six-head capacity: Part No. 01724A (available since 1971)

B. Twelve-head capacity: Part No. 01725A (available since 1971)

4.  INSTALLATION

Refer to appropriate NFPA Installation Standards.

Replaces Form No. F_061614 Rev 17.2

(Added P65 Warning.)

Summary of Contents for MICROFAST VK3271

Page 1: ...ting FM Approval and NFPA 13 installs require a minimum of 7 psi 0 5 bar The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi 0 35 bar Material Standards Frame Casting Brass UNS C84400 or QM Brass Deflector Brass UNS C26000 Bushing Brass UNS C36000 Bulb Glass nominal 3 mm diameter Belleville Spring Sealing Assembly Nickel Alloy coated on both sides with PTFE Tape Screw Brass UNS ...

Page 2: ...ABLE 1 AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Classification Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature2 Bulb Color Ordinary 135 F 57 C 100 F 38 C Orange Ordinary 155 F 68 C 100 F 38 C Red Intermediate 175 F 79 C 150 F 65 C Yellow Intermediate 200 F 93 C 150 F 65 C Green High 286 F 141 C 225 F 107 C Blue Sprinkler Finishes Brass Ch...

Page 3: ...g s current price schedule 2 Metric K factor measurement shown is when pressure is measured in Bar When pressure is measured in kPa divide the metric K factor shown by 10 0 3 This table shows the listings and approvals available at the time of printing Check with the manufacturer for any additional approvals 4 Listed by Underwriters Laboratories Inc for us in the U S and Canada 5 Other colors are ...

Page 4: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Page 5: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Page 6: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Page 7: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Page 8: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...