![Axi STS 6000-P35 Instruction, Operating, & Maintenance Manual Download Page 12](http://html1.mh-extra.com/html/axi/sts-6000-p35/sts-6000-p35_instruction-operating-and-maintenance-manual_3036342012.webp)
MAINTENANCE
! IMPORTANT ! It is recommended that only qualified, experienced personnel, familiar
with this equipment, who have read and understood all the instructions in this manual
should install, operate and maintain the system.
! IMPORTANT ! Always disconnect the system from the electric power supply before
working or servicing it. Do not proceed with any maintenance unless the pressure or
vacuum has been released, the system has been allowed to reach ambient temperature
and all fluids have been
drained.
PREVENTATIVE MAINTENANCE
The STS-6000 Automatic Fuel Filtration System should be visually inspected and tested a minimum of
every six months according to the procedure below during light duty cycles. Monthly inspections are
recommended for systems that are being used in excess of an average of 8 hours day and five days a week
.
o
Prior to performing the maintenance procedure ensure that:
o
The electrical sub-panel mounted main disconnect switch is operating properly,
o
the user supplied remote circuit breaker is in the “Off” position, and
o
that all sources of power are isolated from the unit.
o
Proceed only after this has been verified and properly tagged.
o
Drain visible water and sediment from primary filter / coalescer (see Servicing Primary Filter /
coalescer below).
o
Check enclosure and all parts for corrosion and rust.
o
Check locking latches, door and hinge operation.
o
Check cabinet mounting hardware. Tighten as necessary.
o
Check pump/motor hardware for tightness. Pump/motor hardware will loosen after normal
operation due to vibration. This hardware is lock nutted, check all bolts for secure nuts.
o
Check all electrical terminals and connections for tightness.
o
Check all plumbing joints for leaks. Tighten fittings and joints as necessary. Remove
accumulated fuel in drip tray as necessary.
o
Inspect all filters and separators. See section below on filter inspection and service.
Note: If any of the above described alarm test procedures fail or if any alarm trip value
deviates immediately contact AXI International.
Note: All filter elements should be replaced at least every six months.
`