![Axi STS 6000-P35 Instruction, Operating, & Maintenance Manual Download Page 6](http://html1.mh-extra.com/html/axi/sts-6000-p35/sts-6000-p35_instruction-operating-and-maintenance-manual_3036342006.webp)
8
•
10-micron coalescing filter cartridge (other filter elements available)
FUEL CONDITIONER
•
Inline Algae-X Fuel Conditioner eliminates and prevents microbial contamination and the
formation of sediments that naturally occur in diesel fuel.
SECONDARY FILTER
•
Two 3 Micron water blocking spin on filter (other filter elements available)
•
Pressure gauge (stainless steel, liquid filled)
WEATHERPROOF DOUBLE DOOR WALL-MOUNTED ENCLOSURE WITH
LOCKABLE HANDLES / LATCHES
•
14-gauge steel construction with continuously welded seams
•
Concealed hinges
•
Finished in polyester powder coat inside and out over phosphatized surfaces
•
Spill tray with leak detection
•
Louvered side panels
•
Brackets for wall mounting
•
Literature pocket
CARBON
STEEL PLUMBING
PRIMARY INSPECTION
Upon arrival, the STS 6000-P35 Automatic Fuel Filtration System and accessories must be visually
inspected before installation. Improper handling during shipping may cause physical or electrical
problems. Immediately report or note any damages (also concealed ones) to the shipper.
CHECKLIST:
o
If the packing crate shows signs of damage inspect the STS-6000 cabinet for damage. Check the
entire outside of the cabinet for damage that could indicate internal mechanical or electrical
problems.
o
Check locking handles, door and hinge operation.
o
Check pump/motor hardware and all plumbing connections for tightness.
o
Check all electrical terminals and connections for tightness.
INSTALLATION
! IMPORTANT ! It is recommended that only qualified, experienced personnel, familiar
with this type of equipment, who have read and understood all the instructions in this
manual should install, operate and maintain the system.
MOUNTING
The STS-6000 is a totally enclosed system and should be permanently wall mounted on a hard, level
surface. Use provided mounting feet for proper fastening. This weatherproof unit is designed for well-
ventilated indoor or outdoor use within specified temperature range and should be located as close
to the tank as possible.