Disassembly and Exchange
AVENTICS
| PROFINET-IO | R412015162–BDL–001–AE
107
English
7.2
Mounting input/output module(s)
Input and output modules can be added to the valve system.
A maximum of 6 modules (input or output) may be mounted
on one valve system. Observe the permissible current load!
1.
Unscrew the left end plate (
2
) from the bus coupler (
7
) or from
the last input (
5
) or output module (
4
) of the valve system
(2 hexagonal head-socket screws DIN 912 – M4 (
1
), wrench
size 3) and remove from the tie rods (
6
).
2.
Screw the tie rods (
6
) for the input (
5
) or output modules (
4
) on
the existing tie rods (
6
) (2 per input (
5
) or output module (
4
)).
– Ensure that the tie rods (
6
) are flush with the surface!
3.
Attach the (additional) input (
5
) or output module (
4
) to the tie
rods (
6
).
– Make sure the seals (
3
) have been correctly inserted and
that the contacts have been properly connected.
4.
Retighten the left end plate (
2
) after the last input module (
5
)
or output module (
4
) (2 hexagonal socket-head screws
DIN 912 – M4 (
1
), wrench size 3).
Tightening torque: 2.5 to 3 Nm.
5.
Establish the connections (see “Pin assignment for bus
coupler with 7/8" plug for power supply” on page 81).
CAUTION
Applied voltage and high pressure!
Danger of injury from electric shocks and sudden pressure
drops.
O
Make sure the system is not under pressure or voltage
before you exchange the modules.
Summary of Contents for PROFINET-IO
Page 2: ......
Page 114: ...Disposal 114 AVENTICS PROFINET IO R412015162 BDL 001 AE...
Page 174: ...Elimination des d chets 174 AVENTICS PROFINET IO R412015162 BDL 001 AE...
Page 236: ...ndice 236 AVENTICS PROFINET IO R412015162 BDL 001 AE...
Page 347: ...Nyckelordsregister AVENTICS PROFINET IO R412015162 BDL 001 AE 347 Svenska...