Installation
AVENTICS
| INTERBUS | R412005655–BDL–001–AB
91
English
5.4.4
Input assignment in the 16-position
E24V-/16f-IB input module
The total current for all sensor supplies on one valve
system must not exceed 2 A.
Assignment of M12x1
connections on the
16-position E24V-/16f-IB
input module
See chapter 8.2
The M12x1 mating plug is used to connect sensors with 2 signals
to an M12x1 socket. The M12x1 duo-plug is suited for connecting
two separate sensors with 1 signal each to one M12x1 socket.
Max. cable length at inputs: 30 m
5.4.5
Output assignments in the 8-position
A24V-/0.5A-IB output module
4
5
1
3
2
Table 15:
Input assignment in the 16-position E24V/16f-IB input module
Pin
Signal
Assignment
1
P24V
Sensor supply
2
Input 1, 3, 5, 7, 9, 11, 13, 15
Sensor signal
3
PGND
Ground for P24V
4
Input 0, 2, 4, 6, 8, 10, 12, 14
Sensor signal
5
–
Not connected
NOTICE
Every output can deliver a maximum current of 0.5 A.
O
The total current of the outputs of all output modules
connected to the bus coupler may not exceed 6.0 A.
O
The total current of the outputs of all output modules
connected to the power module may not exceed 12.0 A.