Configuration
AVENTICS
| INTERBUS | R412005655–BDL–001–AB
77
English
Fig. 2:
The bus coupler's SMD S1 switch
Once the S1/1, S1/6 and S1/8 switches have been altered,
it is important to reconfigure the bus as these switch
positions affect the entire bus system.
S1/1 and S1/8 switches
presettings
See Fig. 2
Explanations to Tab. 7:
S1/1 switch, data
capacity for valve control
The data capacity can be set to either 1 word or 2 words.
1 word = 16 output bits for 8 valves
2 words = 32 output bits for 16 valves
NOTICE
The SMD switches can only be adjusted when the power
supply is switched off, i. e. in a voltage-free state!
S1
BTN
POWER
3
1
2
3
4
5
6
7
8
F
F
O
N
O
Table 7:
Presettings, SMD S1 switch assignment
Switch/Function
Effect
S1/1
Data capacity for valve control
ON
1 word
OFF
2 words
S1/8
Baud rate
ON
500 kBaud
OFF
2 MBaud