Installation
90
AVENTICS
| INTERBUS | R412005655–BDL–001–AB
Power consumption for
the supply voltage
(bus coupler)
The power consumption should be set accordingly. When
choosing suitable cable cross-sections, the cable length and the
emitted currents should be considered:
5.4.3
Connection of I/O modules
The electrical inputs and outputs are connected to the
I/O modules with M12x1 coupling plugs (accessories). In order
to comply to the protection class IP65, unassigned sockets
should be covered with the M12x1protective cap (accessories).
The inputs are to be wired in accordance with Tab. 15, the
outputs in accordance with Tab. 16.
Table 14:
Power consumption on the bus coupler
Connection/Supply
Total current
US1
Voltage supply 1
Max. 2.4 A
L24V
Logic 0.4 A
P24V
Inputs max. 2.0 A
US2
Voltage supply 2
Max. 8.3 A
P24VV
Valves max. 2.3 A
P24VA
Outputs max. 6.0 A
CAUTION
Applied voltage
Danger of injury from electric shocks.
O
When connecting peripheral devices (I/O interface),
observe the requirements to protect against accidental
contact in accordance with EN 50178, classification
VDE 0160.