Changes on the Detection Loop
Installation Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-INSTAL/DGB, Rev. C, 2016-29-02,
Autronica Fire and Security AS
Page 79
14.7 Major Changes / Clear Loop Config. - Restart
System
Note that, when major changes are to be done on an existing
detection loop, i.e. a large amount of points on an existing
detection loop are to be removed and others are to be added, it is
recommended to use the command Clear Loop Config. - Restart
System. This command allows you to delete
all
points on a
selected
detection loop, meaning that you can start from the
beginning configuring the detection loop in question.
For further information, refer to the Configuration Handbook.