Cable Specifications
Installation Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-INSTAL/DGB, Rev. C, 2016-29-02,
Autronica Fire and Security AS
Page 19
8.2.2 Table for High Current Detectors and I/O units
Detection
Loop
current
setting
(mA)
Max cable
resistance
(ohm)
Cable
length
(m) for
AWG 20
(0,5mm²)
Cable
length (m)
for
AWG 18
(0,75mm²)
Cable
length
(m) for
AWG 17
(1,0mm²)
Cable
length
(m) for
AWG 15
(1,5mm²)
Cable
length
(m) for
AWG 13
(2,5mm²)
100
112
1600
2400
3200
4800
8000
150
78
1114
1671
2229
3343
5571
200
55
786
1179
1571
2357
3929
250
40
571
857
1143
1714
2857
300
30
429
643
857
1286
2143
350
23
329
493
657
986
1643
400
18
257
386
514
771
1286
8.2.3 Onboard I/O and Power
Maximum
resistance /
capacitance
Wire
Dimensions
(examples)
Maximum
cable
length
Remarks
(
/
μ
F)
(mm
2
)
(AWG)
(m)
Inputs,
Monitored
10m
Inputs,
Non-monitored
50m
Output,
Monitored
(Alarm
Sounder
Circuits)
-
-
2 x 1,5
2 x 0,78
15
18
-
-
Determined by cable loss
(0,5A maximum load)
Output, Relay
-
Output, O.C
100m
Battery
-
-
-
2 x 2,5
2 x 1,5
13
5 m
3m
Maximum battery cable length is
5m
Maximum cable resistance is
0.05 ohm
Mains
-
3 x 1,5
15
-
-