![Autronica Autroprime Installation Handbook Download Page 74](http://html.mh-extra.com/html/autronica/autroprime/autroprime_installation-handbook_3023428074.webp)
Exporting / Importing
Configuration Data
Installation Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-INSTAL/DGB, Rev. C, 2016-29-02,
Autronica Fire and Security AS
Page 74
13.5 Backup Current Configuration
To perform an internal backup of a current configuration, enter the
service menu (see chapter 13.2), then perform the command
Backup Current Configuration.
This command allows you to take an internal backup of the current
configuration.
From the Service Menu, perform the following:
Use the arrow down button to scroll downwards to
Export and Import, then press Enter.
Press the arrow down button to select Backup Current
Configuration, then press Enter.
The following message will appear:
” Create backup of the current configuration. Please save the
configuration if configuration has been changed”.
To execute the command, use the left arrow button to select
Accept, then press Enter.
13.6 Select Configuration & Restart System
This command allows you to restart the system by using one of the
configuration files available (current configuration, imported
configuration or backup configuration).
From the Service Menu, perform the following:
Use the arrow down button to scroll downwards to
Export and Import, then press Enter.
Press the arrow down button to select Select Configuration &
Restart System, then press Enter twice.
The following message will appear:
” Restart the system by using one of the configurations
available”.
If several configurations are available, use the left/right arrow
buttons to select the configuration (Current Configuration,
Imported Configuration or Backup Configuration).
Press Enter.
Make sure to save all recent configuration changes (using the Save
Configuration command in the System Settings menu, chapter 13.7)
before executing the Backup Current Configuration command.