Startup
Installation Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-INSTAL/DGB, Rev. C, 2016-29-02,
Autronica Fire and Security AS
Page 65
Step Actions to be taken
5
Turn the key clockwise.
To enter Service Mode, press and hold down the Enter button for a few seconds.
Use the Arrow down button to select Service, then press Enter.
Select System Settings (the uppermost menu selection which is highlighted), then
press Enter.
Select
Save Configuration
(the uppermost menu selection which is highlighted),
then press Enter twice.
Type the Operator Name, then press Enter.
Type the Site Configuration Version, then press Enter.
Type a Description, then press Enter.
Press Enter once more to confirm.
Use the Arrow down button to select
Restart System
.
Use the left Arrow button to select Accept, then press Enter.
The message “System is now shutting down…” will appear, and the system will
reboot automatically.
The system topology is shown in the display. Press the Cancel/Back button to reveal
the idle display.
6
Before leaving the system unattended, all faults should be corrected.
Any fault preventing the system from detecting or reporting a fire must be corrected.
The system now functions with the default configuration. Site-
specific configuration can now be carried out. For details on
system configuration and examples on how to configure a site-
specific configuration, refer to the Configuration Handbook.