Cable Connections
Installation Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-INSTAL/DGB, Rev. C, 2016-29-02,
Autronica Fire and Security AS
Page 43
9.9.2 Connections (J4) for a cabinet with external BS-210 and
no external panel bus
If the Operator Panel BS-210 is to be placed outside a cabinet, and
no external panel bus (with additional panels) is to be connected to
the cabinet, the Auxiliary terminal connector J4 must be used.
Note:
From the factory, the configuration is by default prepared for a
standalone panel with integrated BS-210.
If the Operator Panel BS-210 is to be placed outside the
cabinet and no external panel bus is to be connected to the
cabinet,
the configuration of the panel has to be changed
during commissioning in order to achieve redundancy and fault
monitoring of the panel bus.
Configuration change:
The configuration of the panel connection (Service
Menu/System Settings/“Set Operator Panel connection”) must
be set to “J4, Auxiliary terminal block” (connector J4) during
commissioning/reconfiguration.
Summary of Contents for Autroprime