Switches and Indicators on
the Main Board
Installation Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-INSTAL/DGB, Rev. C, 2016-29-02,
Autronica Fire and Security AS
Page 67
12.3 Dip-switches for Mode Settings (S2)
Switch Description
Default
S2.1
Boot select, if ON, boot from external memory, if OFF
boot from internal boot ROM. In normal operation set
to On.
ON
S2.2
Not in use.
OFF
S2.3
Run without batteries
OFF
S2.4 Market
selection.
Select between Land (BS-200) and
Maritime (BS/200M)
Land: S2.4 ON
Maritime: S2.4 OFF
ON
S2.5
ON: disable Deep Discharge function (relay always
kept closed). Refer to chapter 12.5.
OFF
12.4 Battery Short-circuit Protection
The battery circuit is protected with an automatic resettable
electronic fuse that prevents system shutdown in case of short-
circuit in the battery circuit.
Internal Cabling
Connector Description
Power Supply
J3.1 Charge
Control VCON
J3.2
Charge Control FB
-V
J3.3 Mains
OK
PSF
J3.4 Battery
Temperature
Sense +
Battery
Temperature
Sensor
J3.5 Battery
Temperature
Sense -
J1.3 Charger
+24V
+V
J1.4 Charger
0V
-V