Cable Connections
Installation Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-INSTAL/DGB, Rev. C, 2016-29-02,
Autronica Fire and Security AS
Page 38
9.8.4 Auxiliary Term inal Block J4
The auxiliary spring-loaded connection block J4 is capable of
cables up to 0,5mm
2
single or multi stranded cables. If multi
stranded cables are used, cable crimps should be used.
J4- Description
1
O.P. +24V 1
Connections to Operator Panel
(Return/Input for redundancy)
2
O.P. 0V 1
3
O.P. A 1
4
O.P. B 1
5
O.P. +24V 2
6
O.P. 0V 2
7
8
O.P. B 2
9
Panel Bus in A
Connections to panel bus. Connects from
unit to unit.
(Return/Input for redundancy)
10
Panel Bus in B
11
Panel Bus Out A
12
Panel Bus Out B
9.8.5 Add-on Network Interface, J5
J5- Description
1
External network interface reset
2
To RX on network card, RS232 level
3
To TX on network card, RS232 level
4 Vbatt
5 Protective
0V
6 +24.0V
7
Reset to external loopers
8 +5.0V
9
To TX on external loopers, TTL level RS232
10 Connector
key
11
To RX on external loopers, TTL level RS232
12 0V
13 Protective
0V
14 0V