55
►
Observe the instructions of the mounting accessories�
►
Use a lubricating paste which is suitable and approved for the applica-
tion� Grease the threads of the process connection, adapter and sensor�
Ensure no grease is applied to the sensor tip�
►
Take the tightening torques of sensor and fixing elements into account�
The following tightening torques apply to AS005: 25 Nm
5.1 Installation position
General
The sensor tip must be completely surroun-
ded by the medium�
≥
15 mm
Internal pipe
diameter (diA)
Immersion depth
< 120 mm
~ 15 mm
≥ 120 mm
~ ⅛ diA
Table 1: Immersion depth of the probe
For strong leverage on the measuring probe, e�g� due to high-viscosity or
strongly flowing media:
►
Do not exceed the immersion depth indicated in table 1�
UK