Flow measurement
Temperature monitoring
MEW
MAW
FEP
FrP
=100
%
0
%
120
%
100
% 120
%
130
%
OL Err
1
2
5
4
3
FOU=On
FOU=OFF
UL
Err
MEW
MAW
FEP
FSP
FrP
=100
%
120
%
0
%
130
%
1
2
5
4
3
FOU=On
FOU=OFF
100
% 120
%
OL Err
UL
Err
Figure 2: Output curve frequency output
MAW: Initial value of the measuring range for non-scaled measuring range
MEW: Final value of the measuring range for non-scaled measuring range
FSP: Frequency start point with scaled measuring range (only temperature)
FEP: Frequency end point with scaled measuring range
FrP: Frequency signal for upper measured value
OL:
Above the display range
Err:
The unit is in the error state
1
Frequency signal (FrP at factory setting = 100 Hz)
2
Measured value (flow or temperature in % MEW)
3
Display range
4
Measuring range
5
Scaled measuring range
4.8 Measured value damping (dAP)
The damping time enables setting how many seconds after the output signal has
reached 63 % of the final value if the flow value changes suddenly� The set dam-
ping time stabilises the outputs, the display and the process value transfer via the
IO-Link interface. The signals [UL] and [OL] (→ 13 Troubleshooting) are defined
under consideration of the damping time�